7.3 Connection Examples for Control of
Motor with External Signal Provider
NOTICE!
The following examples refer only to the adjustable
frequency drive control card (right LCP), not the filter.
7.3.1 Start/Stop
Terminal 18 = 5-10 Terminal 18 Digital Input [8] Start
Terminal 27 = 5-12 Terminal 27 Digital Input [0] No
operation (Default coast inverse)
Terminal 37 = Safe stop
Figure 7.5 Start/Stop Parameters
7.3.2
Pulse Start/Stop
Terminal 18 = 5-10 Terminal 18 Digital Input [9] Latched
start
Terminal 27= 5-12 Terminal 27 Digital Input [6] Stop inverse
Terminal 37 = Safe torque off
Figure 7.6 Pulse Start/Stop Parameters