3.4.4 RFI Switch
Line power supply isolated from ground
If the adjustable frequency drive is supplied from an
isolated line power source or TT/TN-S line power with
grounded leg, turn off the RFI switch via 14-50 RFI 1 on
both adjustable frequency drive and the filter. For further
reference, see IEC 364-3. When optimum EMC performance
is needed, parallel motors are connected, or the motor
cable length is above 82 ft [25 m], set 14-50 RFI 1 to [ON].
In OFF, the internal RFI capacitors (filter capacitors)
between the chassis and the intermediate circuit are cut
off to avoid damage to the intermediate circuit and reduce
ground capacity currents (IEC 61800-3).
Refer to the application note VLT on IT line power. It is
important to use isolation monitors that work together
with power electronics (IEC 61557-8).
3.4.5
Shielded Cables
It is important to connect shielded cables properly to
ensure high EMC immunity and low emissions.
Connection can be made using either cable connectors
or clamps:
EMC cable connectors: generally available cable
connectors can be used to ensure an optimum
EMC connection.
EMC cable clamp: Clamps allowing easy
connection are supplied with the unit.
3.4.6
Motor Cable
Connect the motor to terminals U/T1/96, V/T2/97, W/T3/98,
on the far right of the unit. Ground to terminal 99. All
types of 3-phase asynchronous standard motors can be
used with an adjustable frequency drive. The factory
setting is for clockwise rotation with the adjustable
frequency drive output connected as follows:
Terminal No. Function
96, 97, 98, 99 Line power U/T1, V/T2, W/T3
Ground
Table 3.4 Terminal Functions
Terminal U/T1/96 connected to U-phase
Terminal V/T2/97 connected to V-phase
Terminal W/T3/98 connected to W-phase
The direction of rotation can be changed by switching two
phases in the motor cable or by changing the setting of
4-10 Motor Speed Direction.
Motor rotation check can be performed via 1-28 Motor
Rotation Check and following the steps shown in the
display.
175HA036.11
U
1
V
1
W
1
96 97 98
FC
Motor
U
2
V
2
W
2
U
1
V
1
W
1
96 97 98
FC
Motor
U
2
V
2
W
2
Figure 3.16 Motor Rotation Check
F-frame requirements
Use motor phase cables in quantities of 2, resulting in 2, 4,
6, or 8 to obtain an equal number of wires on both
inverter module terminals. The cables are required to be
equal length within 10% between the inverter module
terminals and the first common point of a phase. The
recommended common point is the motor terminals.
Output junction box requirements
The length, a minimum of 8 ft [2.5 m], and quantity of
cables must be equal from each inverter module to the
common terminal in the junction box.
Installation
Instruction Manual
MG37A222 Danfoss A/S © Rev. 2014-02-07 All rights reserved. 27
3 3

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals