6 Programming
6.1 How to Program the Adjustable
Frequency Drive
6.1.1 Quick Set-up Parameters
0-01 Language
Option: Function:
Defines the language to be used in the
display. The adjustable frequency drive can
be delivered with four different language
packages. English and German are
included in all packages. English cannot be
erased or manipulated.
[0] English Part of Language packages 1 - 4
[1] Deutsch Part of Language packages 1 - 4
[2] Francais Part of Language package 1
[3] Dansk Part of Language package 1
[4] Spanish Part of Language package 1
[5] Italiano Part of Language package 1
Svenska Part of Language package 1
[7] Nederlands Part of Language package 1
[10] Chinese Part of Language package 2
Suomi Part of Language package 1
[22] English US Part of Language package 4
Greek Part of Language package 4
Bras.port Part of Language package 4
Slovenian Part of Language package 3
Korean Part of Language package 2
Japanese Part of Language package 2
Turkish Part of Language package 4
Trad.Chinese Part of Language package 2
Bulgarian Part of Language package 3
Srpski Part of Language package 3
Romanian Part of Language package 3
Magyar Part of Language package 3
Czech Part of Language package 3
0-01 Language
Option: Function:
Polski Part of Language package 4
Russian Part of Language package 3
Thai Part of Language package 2
Bahasa
Indonesia
Part of Language package 2
[52] Hrvatski
1-20 Motor Power [kW]
Range: Function:
Size
related*
[ 0.09 -
3000.00
kW]
Enter the nominal motor power in kW
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
This parameter cannot be adjusted while
the motor is running. This parameter is
visible in LCP if 0-03 Regional Settings is
[0] International.
NOTICE!
Four sizes down, one size up from
nominal unit rating.
1-22 Motor Voltage
Range: Function:
Size
related*
[ 10 -
1000 V]
Enter the nominal motor voltage
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
This parameter cannot be adjusted while
the motor is running.
1-23 Motor Frequency
Range: Function:
Size
related*
[20 -
1000
Hz]
Min - Max motor frequency: 20–1000 Hz.
Select the motor frequency value from the
motor nameplate data. If a value different
from 50 Hz or 60 Hz is selected, it is
necessary to adapt the load independent
settings in 1-50 Motor Magnetization at Zero
Speed to 1-53 Model Shift Frequency. For 87
Hz operation with 230/400 V motors, set the
nameplate data for 230 V/50 Hz. Adapt
4-13 Motor Speed High Limit [RPM] and
parameter 3-03 Maximum Reference to the 87
Hz application.
Programming Instruction Manual
52 Danfoss A/S © Rev. 2014-02-07 All rights reserved. MG37A222