EasyManuals Logo
Home>Danfoss>DC Drives>VLT AutomationDrive FC 302

Danfoss VLT AutomationDrive FC 302 Instruction Manual

Danfoss VLT AutomationDrive FC 302
174 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
4. Press the navigation keys to scroll to parameter
group 0-0* Basic Settings and press [OK].
0-
**
Operation / Display
0.0%
0-0
*
Basic Settings
0-1
*
Set-up Operations
0-2
*
LCP Display
0-3
*
LCP Custom Readout
0.00A 1(1)
130BP087.10
Figure 4.2 0-0* Basic Settings
5. Press the navigation keys to scroll to
0-03 Regional Settings and press [OK].
Figure 4.3 0-03 Regional Settings
6.
Press the navigation keys to select International
or North America as appropriate and press [OK].
(This changes the default settings for a number
of basic parameters. See chapter 6 Programming
for a complete list.)
7. Press [Quick Menu] on the LCP.
8. Press the navigation keys to scroll to parameter
group Q2 Quick Set-up.
9. Press [OK].
Figure 4.4 Q2 Quick Set-up
10. Select language and press [OK].
Figure 4.5 Select Language
11. If a jumper wire is placed between control
terminals 12 and 27 leave 5-12 Terminal 27 Digital
Input at factory default. Otherwise select No
Operation. For adjustable frequency drives with
an optional bypass, no jumper wire is required.
12.
parameter 3-02 Minimum Reference
13.
parameter 3-03 Maximum Reference
14.
3-41 Ramp 1 Ramp-up Time
15.
3-42 Ramp 1 Ramp-down Time
16.
3-13 Reference Site. Linked to Hand/Auto* Local
Remote.
4.4
Local Control Test
CAUTION
MOTOR START!
Ensure that the motor, system and any attached
equipment are ready for start. It is the responsibility of
the user to ensure safe operation under any condition.
Failure to ensure that the motor, system, and any
attached equipment are ready for start could result in
personal injury or equipment damage.
NOTICE!
The [Hand On] key provides a local start command to
the adjustable frequency drive. The [Off] key provides
the stop function.
When operating in local mode, [
] and [
] increase and
decrease the speed output of the adjustable frequency
drive. [] and [] move the display cursor in the numeric
display.
Start-up and Functional Tes... Instruction Manual
42 Danfoss A/S © Rev. 2014-02-07 All rights reserved. MG37A222
44

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals