4 Start-up and Functional Testing
4.1 Pre-start
CAUTION
Before applying power to the unit, inspect the entire installation as detailed in Table 4.1. Check mark those items when
completed.
Inspect for Description
Auxiliary equipment
Look for auxiliary equipment, switches, disconnects, or input fuses/circuit breakers on the input
power side of the adjustable frequency drive or output side to the motor. Ensure that they are ready
for full speed operation.
Check function and installation of any sensors used for feedback to the adjustable frequency drive.
Remove power factor correction caps on motors, if present.
Cable routing
Use separate metallic conduits for each of the following:
input power
motor wiring
control wiring
Control wiring
Check for broken or damaged wires and loose connections.
Check that control wiring is isolated from power and motor wiring for noise immunity.
Check the voltage source of the signals, if necessary.
The use of shielded cable or twisted pair is recommended. Ensure that the shield is terminated
correctly.
Cooling clearance
Make sure that the top and bottom clearance is adequate to ensure proper airflow for cooling.
EMC considerations
Check for proper installation regarding electromagnetic compatibility.
Environmental consider-
ations
See equipment label for the maximum ambient operating temperature limits.
Humidity levels must be 5–95% non-condensing.
Fusing and circuit
breakers
Check for proper fusing or circuit breakers.
Check that all fuses are inserted firmly and in operational condition and that all circuit breakers are
in the open position.
Grounding
The unit requires a ground wire from its chassis to the building ground.
Check for good ground connections that are tight and free of oxidation.
Grounding to conduit or mounting the back panel to a metal surface is not a suitable ground.
Input and output power
wiring
Check for loose connections.
Check that motor and line power are in separate conduits or separated shielded cables.
Panel interior
Make sure that the unit interior is free of debris and corrosion.
Switches
Ensure that all switch and disconnect settings are in the proper positions.
Vibration
Check that the unit is mounted solidly or that shock mounts are used, as necessary.
Check for an unusual amount of vibration.
Table 4.1 Start-up Checklist
Start-up and Functional Tes...
Instruction Manual
40 Danfoss A/S © Rev. 2014-02-07 All rights reserved. MG37A222
44

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals