Control card performance
Scan interval 5 ms
Control card, USB serial communication
USB standard 1.1 (full speed)
USB plug USB type B device plug
NOTICE!
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from ground protection. Use only isolated laptop/PC as connection to
the USB connector on the adjustable frequency drive or an isolated USB cable/drive.
Protection and Features:
•
Electronic thermal motor protection against overload.
•
Temperature monitoring of the heatsink ensures that the adjustable frequency drive trips if the temperature
reaches a predefined level. An overload temperature cannot be reset until the temperature of the heatsink is
below the allowed values.
•
The adjustable frequency drive is protected against short-circuits on motor terminals U, V, W.
•
If a line phase is missing, the adjustable frequency drive trips or issues a warning (depending on the load).
•
Monitoring of the intermediate circuit voltage ensures that the adjustable frequency drive trips if the intermediate
circuit voltage is too low or too high.
•
The adjustable frequency drive is protected against ground faults on motor terminals U, V, W.
11.4
General Technical Data - Filter
Frame size D13 E9 F18
Voltage [V] 380–480 380–480 380–480
Current, RMS [A] 120 210 330 Nominal value
Peak current [A] 340 595 935 Amplitude value of the current
Response time [ms] <0.5
Settling time - reactive current control [ms] <40
Settling time - harmonic current control
(filtering) [ms]
<20
Overshoot - reactive current control [%] <20
Overshoot - harmonic current control [%] <10
Table 11.6 Power Ranges (LHD with AF)
Specifications Instruction Manual
160 Danfoss A/S © Rev. 2014-02-07 All rights reserved. MG37A222