Control card performance
Scan interval 5 ms
Control card, USB serial communication
USB standard 1.1 (full speed)
USB plug USB type B device plug
NOTICE!
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from ground protection. Use only isolated laptop/PC as connection to
the USB connector on the adjustable frequency drive or an isolated USB cable/drive.
Protection and Features:
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the adjustable frequency drive trips if the temperature
reaches a predefined level. An overload temperature cannot be reset until the temperature of the heatsink is
below the allowed values.
The adjustable frequency drive is protected against short-circuits on motor terminals U, V, W.
If a line phase is missing, the adjustable frequency drive trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the adjustable frequency drive trips if the intermediate
circuit voltage is too low or too high.
The adjustable frequency drive is protected against ground faults on motor terminals U, V, W.
11.4
General Technical Data - Filter
Frame size D13 E9 F18
Voltage [V] 380–480 380–480 380–480
Current, RMS [A] 120 210 330 Nominal value
Peak current [A] 340 595 935 Amplitude value of the current
Response time [ms] <0.5
Settling time - reactive current control [ms] <40
Settling time - harmonic current control
(filtering) [ms]
<20
Overshoot - reactive current control [%] <20
Overshoot - harmonic current control [%] <10
Table 11.6 Power Ranges (LHD with AF)
Specifications Instruction Manual
160 Danfoss A/S © Rev. 2014-02-07 All rights reserved. MG37A222
1111

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals