P450 P500 P560 P630
Normal Overload =110% current
for 60 s
HO NO HO NO HO NO HO NO
Typical shaft output at 400 V [kW] 450 500 500 560 560 630 630 710
Typical shaft output at 460 V [hp] 600 650 650 750 750 900 900 1000
Typical shaft output at 480 V [kW] 530 560 560 630 630 710 710 800
Enclosure IP21/54 F18
Output current
Continuous (at 400 V) [A] 800 880 880 990 990 1120 1120 1260
Intermittent (60 s overload)
(at 400 V) [A]
1200 968 1320 1089 1485 1232 1680 1386
Continuous (at 460/480 V) [A] 730 780 780 890 890 1050 1050 1160
Intermittent (60 s overload) (at
460/480 V) [A]
1095 858 1170 979 1335 1155 1575 1276
Continuous kVA (at 400 V) [kVA] 554 610 610 686 686 776 776 873
Continuous kVA (at 460 V) [kVA] 582 621 621 709 709 837 837 924
Continuous kVA (at 480 V) [kVA] 632 675 675 771 771 909 909 1005
Max. Input current
Continuous (at 400 V) [A] 779 857 857 964 964 1090 1090 1227
Continuous (at 460/480 V) [A] 711 759 759 867 867 1022 1022 1129
Max. pre-fuses
1)
[A]
1600
2000
Max. cable size
Motor (mm
2
/AWG
2)
)
8 x 150 (8 x 300 mcm)
Line power (mm
2
/AWG
2
)
8 x 240 (8 x 500 mcm)
Brake (mm
2
/AWG
2)
)
4 x 185 (4 x 350 mcm)
Total LHD loss 400 V AC [kW] 20077 21909 21851 24592 23320 26640 26559 30519
Total backchannel loss 400 V AC
[kW]
16242 17767 17714 19984 18965 21728 21654 24936
Total filter loss 400 V AC [kW] 11047 11747 11705 12771 12670 14128 14068 15845
Total LHD loss 460 V AC [kW] 18855 19896 19842 22353 21260 25030 25015 27989
Total backchannel loss 460 V AC
[kW]
15260 16131 16083 18175 17286 20428 20417 22897
Total filter loss 460 V AC [kW] 10643 11020 10983 11929 11846 13435 13434 14776
Weight, enclosure IP21, IP54
(lbs [kg])
2009
Efficiency
4)
0.96
Output frequency [Hz] 0–600
Heatsink overtemp. trip (°F [°C]) 221 [105]
Power card ambient trip (°F [°C]) 185 [85]
*High overload = 160% torque during 60 s; Normal overload = 110% torque during 60 s
Table 11.3 Line Power Supply 3x380–480 V AC
1) For type of fuse, see chapter 11.5.1 Fuses.
2) American wire gauge.
3) Measured using 16.5 ft. [5 m] shielded motor cables at rated load and rated frequency.
Specifications
Instruction Manual
MG37A222 Danfoss A/S © Rev. 2014-02-07 All rights reserved. 151
11 11

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals