2-20 Release Brake Current
Range: Function:
Size
related*
[ 0 - par.
16-37 A]
Set the motor current for release of the
mechanical brake, when a start condition
is present. The default value is the
maximum current the inverter can provide
for the particular power size. The upper
limit is specified in 16-37 Inv. Max. Current.
NOTICE!
When Mechanical brake control
output is selected but no
mechanical brake is connected, the
function will not work by default
setting due to too low motor
current.
2-21 Activate Brake Speed [RPM]
Range: Function:
Size
related*
[0 - 30000
RPM]
Set the motor speed for activation of
the mechanical brake when a stop
condition is present. The upper
speed limit is specified in
4-53 Warning Speed High.
2-22 Activate Brake Speed [Hz]
Range: Function:
Size related* [ 0 - 5000.0
Hz]
Set the motor frequency for
activation of the mechanical
brake when a stop condition is
present.
2-23 Activate Brake Delay
Range: Function:
0 s* [0 - 5 s] Enter the brake delay time of the coast after
ramp-down time. The shaft is held at zero speed
with full holding torque. Ensure that the
mechanical brake has locked the load before the
motor enters coast mode.
2-24 Stop Delay
Range: Function:
0 s* [0 - 5 s] Set the time interval from the moment when the
motor is stopped until the brake closes. This
parameter is a part of the stopping function.
2-25 Brake Release Time
Range: Function:
0.20 s* [0 - 5 s] This value defines the time it takes for the
mechanical brake to open. This parameter
must act as a timeout when brake feedback is
activated.
2-26 Torque Ref
Range: Function:
0 %* [ 0 - 0 %]
2-27 Torque Ramp Up Time
Range: Function:
0.2 s* [0 - 5 s] The value defines the duration of the torque
ramp in clockwise direction.
2-28 Gain Boost Factor
Range: Function:
1 * [0 - 4 ] Only active in flux closed-loop. The function
ensures a smooth transition from torque control
mode to speed control mode when the motor
takes over the load from the brake.
Programming Instruction Manual
62 Danfoss A/S © Rev. 2014-02-07 All rights reserved. MG37A222
66

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals