EasyManuals Logo
Home>Danfoss>DC Drives>VLT CDS 803

Danfoss VLT CDS 803 User Manual

Danfoss VLT CDS 803
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
Speed
Speed
Start
speed
Start-up sequence
Time
Time
Compressor
start minimum
speed
A18, Start
failed
Compressor start
maximum time to trip
e30bj077.10
Illustration 2: Compressor Start-up Sequence
3.2.1.2 Compressor Minimum Speed Detection
To avoid a malfunction inside the compressor due to missing or low lubrication the VLT® Compressor Drive CDS 803 protects the
compressor if the speed drops below the minimum speed detection limit for too long.
In case of excessive low speed the drive issues Alarm 49, Speed limit.
e30bj078.10
Speed
Motor speed
low limit
Compressor
minimum
speed for trip
Minimum
speed
detection
timer start
Illustration 3: Minimum Speed Detection
AJ330233902305en-000201 / 130R0596 | 13Danfoss A/S © 2021.05
Product Overview
VLT® Compressor Drive CDS 803
Design Guide

Table of Contents

Other manuals for Danfoss VLT CDS 803

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CDS 803 and is the answer not in the manual?

Danfoss VLT CDS 803 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CDS 803
CategoryDC Drives
LanguageEnglish

Related product manuals