EasyManuals Logo
Home>Danfoss>DC Drives>VLT CDS 803

Danfoss VLT CDS 803 User Manual

Danfoss VLT CDS 803
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #60 background imageLoading...
Page #60 background image
1
Aluminum-clad with copper wire.
2
Twisted copper wire or armored steel wire cable.
3
Single-layer braided copper wire with varying per-
centage shield coverage. This is the typical reference
cable.
4
Double-layer braided copper wire.
5
Twin layer of braided copper wire with a magnetic,
shielded/armored intermediate layer.
6
Cable that runs in copper tube or steel tube.
7
Lead cable with 1.1 mm (0.04 in) wall thickness.
6.5.7 Shielded Control Cables
Usually, the preferred method is to secure control and serial communication cables with shielding clamps provided at both ends to
ensure the best possible high frequency cable contact.
If the ground potential between the drive and the PLC is different, electric noise could disturb the entire system. Solve this problem
by fitting an equalizing cable as close as possible to the control cable. Minimum cable cross-section: 16 mm
2
(6 AWG).
1
2
PE
FC
PE
PLC
e30bb922.12
PE PE
<10 mm
Illustration 38: Shielding Clamps at Both Ends
1
Minimum 16 mm
2
(6 AWG)
2
Equalizing cable
6.5.7.1 50/60 Hz Ground Loops
With long control cables, ground loops may occur. To eliminate ground loops, connect 1 end of the shield to the ground with a
100 nF capacitor (keeping leads short).
100nF
FC
PE
PE
PLC
<10 mm
e30bb609.12
Illustration 39: Connection with a 100 nF Capacitor
6.5.7.2 Avoid EMC Noise on Serial Communication
This terminal is connected to ground via an internal RC link. Use twisted-pair cables to reduce interference between conductors. The
recommended method is shown in the following illustration.
PE
FC
PE
FC
e30bb923.12
PE PE
69
68
61
69
68
61
1
2
<10 mm
Illustration 40: Twisted-pair Cables
1
Minimum 16 mm
2
(6 AWG)
2
Equalizing cable
Alternatively, the connection to terminal 61 can be omitted.
AJ330233902305en-000201 / 130R059660 | Danfoss A/S © 2021.05
Electrical Installation
Considerations
VLT® Compressor Drive CDS 803
Design Guide

Table of Contents

Other manuals for Danfoss VLT CDS 803

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CDS 803 and is the answer not in the manual?

Danfoss VLT CDS 803 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CDS 803
CategoryDC Drives
LanguageEnglish

Related product manuals