1.9 Power-dependent Specifications
FC 302 N90K N110 N132 N160 N200 N250
High/Normal Load* HO NO HO NO HO NO HO NO HO NO HO NO
Typical Shaft output at 400 V [kW] 90 110 110 132 132 160 160 200 200 250 250 315
Typical Shaft output at 460 V [hp] 125 150 150 200 200 250 250 300 300 350 350 450
Typical Shaft Output at 500 V [kW] 110 132 132 160 160 200 200 250 250 315 315 355
Enclosure IP21 D1h D1h D1h D2h D2h D2h
Enclosure IP54 D1h D1h D1h D2h D2h D2h
Enclosure IP20 D3h D3h D3h D4h D4h D4h
Output current
Continuous (at 400 V) [A] 177 212 212 260 260 315 315 395 395 480 480 588
Intermittent (60 s overload) (at 400 V) [A] 266 233 318 286 390 347 473 435 593 528 720 647
Continuous (at 460/500 V) [A] 160 190 190 240 240 302 302 361 361 443 443 535
Intermittent (60 s overload) (at 460/500 V)
[kVA]
240 209 285 264 360 332 453 397 542 487 665 588
Continuous kVA (at 400 V) [kVA] 123 147 147 180 180 218 218 274 274 333 333 407
Continuous kVA (at 460 V) [kVA] 127 151 151 191 191 241 241 288 288 353 353 426
Continuous kVA (at 500 V) [kVA] 139 165 165 208 208 262 262 313 313 384 384 463
Max. input current
Continuous (at 400 V) [A] 171 204 204 251 251 304 304 381 381 463 463 567
Continuous (at 460/500 V) [A] 154 183 183 231 231 291 291 348 348 427 427 516
Max. cable size: line power, motor, brake
and load share [mm
2
(AWG
2)
)]
5)
2x95
(2x3/0)
2x185
(2x350 mcm)
Max. external electrical fuses [A]
1
315 350 400 550 630 800
Estimated power loss at 400 V [W]
4
2031 2559 2289 2954 2923 3770 3093 4116 4039 5137 5005 6674
Estimated power loss at 460 V [W] 1828 2261 2051 2724 2089 3628 2872 3569 3575 4566 4458 5714
Weight, enclosure IP21, IP54 kg (lbs) 62 (135) 125 (275)
Weight, enclosure IP20 kg (lbs) 62 (135) 125 (275)
Efficiency
4)
0.98
Output frequency 0–800 Hz 0–600 Hz
*High overload = 150% current for 60 s, Normal overload = 110% current for 60 s
Table 1.11 Line Power Supply 3x380–500 V AC
Introduction Service Manual
MG94A222 Danfoss A/S © Rev. 2014-02-10 All rights reserved. 13
1
1

Table of Contents

Other manuals for Danfoss VLT FC 100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 and is the answer not in the manual?

Danfoss VLT FC 100 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100
CategoryDC Drives
LanguageEnglish

Related product manuals