11.2.13 Balance/High Frequency Card
To remove or reinstall the balance/high frequency card for 240/400 V AC or 690 V AC drives, use the following steps. Refer
to Illustration 11.7.
Disassembly in 240/400 V AC units
1. Remove the power terminal mounting plate. Refer
to chapter 11.2.11 Power Terminal Mounting Plate.
2. Unplug the cable from the MK100 connector on
the balance/high frequency card.
3. Remove 1 standoîš‚ (8 mm) from the corner of the
card.
4. Remove 3 nuts (8 mm) from the card. Two of the
nuts also hold in place the DC(+) and DC(-) wires.
5. Remove the balance/high frequency card and
insulator sheet from the drive.
Reassembly in 240/400 V AC units
Tighten hardware according to chapter 14.1 Fastener Torque
Ratings.
1. Place the insulator sheet and balance/high
frequency card in the drive.
2. Fasten 3 nuts (8 mm) in the card. Two of the nuts
also hold in place the DC(+) and DC(-) wires.
3. Fasten 1 standoîš‚ (8 mm) in the corner of the
card.
4. Connect the cable to the MK100 connector on
the balance/high frequency card.
5. Replace the power terminal mounting plate. Refer
to chapter 11.2.11 Power Terminal Mounting Plate.
Disassembly in 690 V AC units
1. Remove the power terminal mounting plate. Refer
to chapter 11.2.11 Power Terminal Mounting Plate.
2. Unplug the cable from the MK100 connector on
the balance/high frequency card.
3. Remove 1 standoîš‚ (8 mm) from the corner of the
card.
4. Remove 3 nuts (8 mm) and 1 screw (T20) from
the card. One of the nuts and the screw also hold
in place the DC(+) and DC(-) wires.
5. Remove the balance/high frequency card and
insulator sheet from the unit.
Reassembly in 690 V AC units
Tighten hardware according to chapter 14.1 Fastener Torque
Ratings.
1. Place the insulator sheet and balance/high
frequency card in the unit.
2. Fasten 3 nuts (8 mm) and 1 screw (T20) in the
card. One of the nuts and the screw also hold in
place the DC(+) and DC(-) wires.
3. Fasten 1 standoîš‚ (8 mm) in the corner of the
card.
4. Connect the cable to the MK100 connector on
the balance/high frequency card.
5. Replace the power terminal mounting plate. Refer
to chapter 11.2.11 Power Terminal Mounting Plate.
D2h/D4h/D7h/D8h/J9 Unit Dis... Service Guide
MG94A502 Danfoss A/S © 02/2019 All rights reserved. 203
11 11

Table of Contents

Other manuals for Danfoss VLT FC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC Series and is the answer not in the manual?

Danfoss VLT FC Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC Series
CategoryDC Drives
LanguageEnglish

Related product manuals