6.4 Visual Inspection
Table 6.1 lists conditions that require visual inspection as part of any initial troubleshooting procedure.
Inspect for Description
Auxiliary equipment Check auxiliary equipment, switches, disconnects, or input fuses/circuit breakers on the input side of the
drive or the output side to the motor. Check the function and installation of pressure sensors, encoders,
or other devices that provide feedback to the drive.
Cable routing Avoid routing the following in parallel:
•
Motor wiring
•
Mains wiring
•
Signal wiring
If parallel routing is unavoidable, maintain a separation of 150–200 mm (6–8 in) between cables, or
separate them with a grounded conductive partition. Avoid routing cables through free air.
Control wiring Check for broken or damaged wires and connections. In parallel drive systems, check connections
between the control shelf and the modules. Check the voltage source of the signals. Use of shielded
cable or a twisted pair is recommended. Ensure that the shield is terminated correctly. See
chapter 4.9 Shielded Cable Grounding.
Cooling Check the operation of all cooling fans. Check the door lters on IP21 (UL type 1)/IP54 (UL type 12)
units. Check for blocked air passages. Verify that the bottom gland plate is installed. Check the positive
and negative interconnections between modules.
DC fuse microswitch In parallel drive systems, check that microswitches have been snapped properly on to DC fuse xtures.
DC fuse mounting In parallel drive systems, check both ends of DC fuses for loose connections.
Display Check the LCP display for warning/alarm messages, system status, and fault history.
Interior Check that the drive interior is free of dirt, metal chips, moisture, and corrosion. Check for burnt or
damaged power components, or carbon deposits resulting from component failure. Check for cracks in
the housings of power semiconductors, or for pieces of broken component housings inside the unit.
EMC considerations Check for proper installation regarding electromagnetic compatibility (EMC). Refer to the drive operating
instructions and chapter 7.3 Electromagnetic Compatibility.
Environmental conditions
The drive can operate within a maximum ambient temperature of 50 °C (122 °F). Humidity levels must
be less than 95% non-condensing. Check for harmful airborne contaminates such as sulphur-based
compounds.
Grounding The drive requires a dedicated ground wire from its enclosure to the building ground. Grounding the
motor to the drive enclosure is recommended. The use of a conduit or mounting the drive onto a metal
surface is not considered a suitable ground. Check that ground connections are tight and free of
oxidation.
Input power wiring Check for loose connections, proper fusing, and blown fuses. In parallel drive systems, check cable length
and cross-section imbalance between the terminals of the modules.
Motor Check the nameplate ratings of the motor. Ensure that the motor ratings correspond with the drive
ratings. Check that the motor parameters (parameter 1-20 Motor Power [kW] to parameter 1-25 Motor
Nominal Speed) are set according to the motor ratings.
Output to motor wiring Check for loose connections. Check for switching components in the output circuit. Check for faulty
contacts in the switchgear. In parallel drive systems, check for proper interconnections between the
modules. Check cable length and cross-section imbalance between the terminals of the modules. One
missing wire can cause an overcurrent trip.
Programming Make sure that the drive parameter settings are correct according to motor, application, and I/O congu-
ration.
Proper clearance Drives require adequate top and bottom clearance to ensure proper airow for cooling. Drives with
exposed heat sinks (in the back) must be mounted on a at solid surface.
Vibration Look for unusual amounts of vibration around the drive. Mount the unit solidly or use shock mounts.
Table 6.1 Visual Inspection
Troubleshooting Service Guide
MG94A502 Danfoss A/S © 02/2019 All rights reserved. 61
6
6

Table of Contents

Other manuals for Danfoss VLT FC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC Series and is the answer not in the manual?

Danfoss VLT FC Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC Series
CategoryDC Drives
LanguageEnglish

Related product manuals