EasyManuals Logo
Home>Danfoss>DC Drives>VLT FC Series

Danfoss VLT FC Series Service Guide

Danfoss VLT FC Series
370 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #322 background imageLoading...
Page #322 background image
14.1.2 Unique Torque Values in E1h–E4h Drives
Some fasteners in E1h–E4h drives require unique, non-standard torque values. Refer to Illustration 14.1 for the type and
location of these fasteners.
130BF930.10
1
2
3
4
5
1 All M4 fasteners
Torque: 2.27 Nm (20.1 lb-in)
4 6 M5 fasteners attaching gate drive card
Torque: 2.27 Nm (20.1 lb-in)
2 3 M5 fasteners
Torque: 3.91 Nm (34.6 lb-in)
5 All M5 fasteners attaching input plates to side mounting rail
Torque: 3.91 Nm (34.6 lb-in)
3 All gasketed M5 fasteners except door screws
Torque: 3.91 Nm (34.6 lb-in)
– –
Illustration 14.1 Unique Torque Values, E1h–E4h Drives