Write data LO (Register 4: 1049)
Write data HI (Register 4: 1050)
Write data LO (Register 4: 1050)
Response
The normal response returns the follower address, function code, starting address, and quantity of registers preset.
Table 81: Response
8.10.8 Read/Write Multiple Registers (17 hex)
Description
This function code performs a combination of 1 read operation and 1 write operation in a single MODBUS transaction. The write
operation is performed before read.
Query
The query message specifies the starting address and number of holding registers to be read as well as the starting address, number
of holding registers, and the data to be written. Holding registers are addressed starting at 0. Example of a request to set parameter
1-24 Motor Current to 738 (7.38 A) and read parameter 3-03 Maximum Reference which has value 50000 (50,000 Hz):
Table 82: Query
Reading starting address HI
0B (Register address 3029)
D5 (Register address 3029)
02 (Parameter 3-03 Maximum Reference is 32 bits long, that is, 2 registers)
Write starting address HI
04 (Register address 1239)
Write starting address LO
D7 (Register address 1239)
AJ363928382091en-000101 / 130R0983124 | Danfoss A/S © 2021.04
RS485 Installation and Set-up
VLT® Flow Drive FC 111
Design Guide