Energy efficiency class
(2)
1
Refer to chapter Derating for:
Derating for high ambient temperature.
Derating for high altitude.
2
Determined according to EN 50598-2 at:
Rated load.
90% rated frequency.
Switching frequency factory setting.
Switching pattern factory setting.
9.2.14 Ambient Conditions (H13–H14)
Enclosure protection rating
Vibration test (standard/ruggedized)
5%-95% (IEC 721-3-3; Class 3K3 (non-condensing) during opera-
tion)
Aggressive environment (IEC 60068-2-43) H
2
S test
Aggressive gases (IEC 60721-3-3)
Test method according to IEC 60068-2-43
Ambient temperature (at SFAVM switching mode)
Maximum 55° C (131° F)
(1)
- with full output power of typical EFF2 motors (up to 90% output
current)
Maximum 50° C (122° F)
(1)
- at full continuous FC output current
Maximum 45° C (113° F)
(1)
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced speed performance
Temperature during storage/transport
-25 to +65/70 °C (-13 to +149/158 °F)
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
(2)
1
Determined according to EN 50598-2 at:
Rated load.
90% rated frequency.
Switching frequency factory setting.
Switching pattern factory setting.
2
For more information on derating, see chapter Derating.
AJ363928382091en-000101 / 130R0983 | 137Danfoss A/S © 2021.04
General Specifications
VLT® Flow Drive FC 111
Design Guide