6.3 Special Conditions
6.3.1 Derating for Ambient Temperature
and Switching Frequency
The ambient temperature measured over 24 hours should
be at least 5 °C (9° F) lower than the maximum ambient
temperature that is specified for the adjustable frequency
driver. If the adjustable frequency drive is operated at a
high ambient temperature, the continuous output current
should be decreased. For derating curve, see VLT
®
HVAC
Basic Drive Design Guide.
6.3.2
Derating for Low Air Pressure and
High Altitudes
The cooling capability of air is decreased at low air
pressure. For altitudes above 2000 m (6562 ft), contact
Danfoss regarding PELV. Below 1000 m (3281 ft) altitude,
no derating is necessary. Above 1000 m (3281 ft), the
ambient temperature or the maximum output current
should be decreased. Decrease the output by 1 % per
100 m (328 ft) altitude above 1000 m (3281 ft) or reduce
the maximum ambient temperature by 1 °C per 200 m
(656 ft).
Specifications VLT®HVAC Basic Drive FC 101
54 Danfoss A/S © 08/2014 All rights reserved. MG18A622
66

Other manuals for Danfoss VLT HVAC Basic Drive FC 101

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Basic Drive FC 101 and is the answer not in the manual?

Danfoss VLT HVAC Basic Drive FC 101 Specifications

General IconGeneral
BrandDanfoss
ModelVLT HVAC Basic Drive FC 101
CategoryDC Drives
LanguageEnglish

Related product manuals