5.2.5 4-** Limits/Warnings
Param
eter #
Parameter description Default value 4 set-up Change during
operation
Conversion
index
Type
4-1* Motor Limits
4-10 Motor Speed Direction [2] Both directions All set-ups FALSE - Uint8
4-12 Motor Speed Low Limit [Hz] 0 Hz All set-ups FALSE -1 Uint16
4-14 Motor Speed High Limit [Hz] 65 Hz All set-ups FALSE -1 Uint16
4-16 Torque Limit Motor Mode ExpressionLimit All set-ups TRUE 0 Uint16
4-17 Torque Limit Generator Mode 100 % All set-ups TRUE 0 Uint16
4-18 Current Limit ExpressionLimit All set-ups TRUE 0 Uint16
4-19 Max Output Frequency ExpressionLimit All set-ups FALSE -1 Uint16
4-2* Limit Factors
4-20 Torque Limit Factor Source [0] No function All set-ups TRUE - Uint8
4-21 Speed Limit Factor Source [0] No function All set-ups TRUE - Uint8
4-22 Break Away Boost [0] O All set-ups FALSE - Uint8
4-3* Motor Fb Monitor
4-30 Motor Feedback Loss Function [2] Trip All set-ups TRUE - Uint8
4-31 Motor Feedback Speed Error 20 Hz All set-ups TRUE 0 Uint16
4-32 Motor Feedback Loss Timeout 0.05 s All set-ups TRUE -2 Uint16
4-4* Adj. Warnings 2
4-40 Warning Freq. Low ExpressionLimit All set-ups TRUE -1 uint16
4-41 Warning Freq. High ExpressionLimit All set-ups TRUE -1 uint16
4-42 Adjustable Temperature Warning 0 N/A All set-ups TRUE 0 Uint8
4-5* Adj. Warnings
4-50 Warning Current Low 0 A All set-ups TRUE -2 Uint32
4-51 Warning Current High ExpressionLimit All set-ups TRUE -2 Uint32
4-54 Warning Reference Low -4999 N/A All set-ups TRUE -3 Int32
4-55 Warning Reference High 4999 N/A All set-ups TRUE -3 Int32
4-56 Warning Feedback Low
-4999
ProcessCtrlUnit All set-ups TRUE -3 Int32
4-57 Warning Feedback High
4999
ProcessCtrlUnit All set-ups TRUE -3 Int32
4-58 Missing Motor Phase Function [1] On All set-ups FALSE - Uint8
4-6* Speed Bypass
4-61 Bypass Speed From [Hz] 0 Hz All set-ups TRUE -1 Uint16
4-63 Bypass Speed To [Hz] 0 Hz All set-ups TRUE -1 Uint16
5.2.6 5-** Digital In/Out
Param
eter #
Parameter description Default value 4 set-up Change during
operation
Conversion
index
Type
5-0* Digital I/O mode
5-00 Digital I/O Mode [0] PNP 1 set-up FALSE - Uint8
5-01 Terminal 27 Mode [0] Input All set-ups TRUE - Uint8
5-1* Digital Inputs
5-10 Terminal 18 Digital Input [8] Start All set-ups TRUE - Uint8
5-11 Terminal 19 Digital Input [10] Reversing All set-ups TRUE - Uint8
5-12 Terminal 27 Digital Input ExpressionLimit All set-ups TRUE - Uint8
5-13 Terminal 29 Digital Input [14] Jog All set-ups TRUE - Uint8
5-14 Terminal 32 Digital Input [0] No operation All set-ups TRUE - Uint8
5-15 Terminal 33 Digital Input [16] Preset ref bit 0 All set-ups TRUE - Uint8
5-19 Terminal 37/38 SAFE STOP [1] Safe Stop Alarm 1 set-up TRUE - Uint8
5-3* Digital Outputs
Parameter Lists
VLT
®
Midi Drive FC 280
120 Danfoss A/S © 12/2015 All rights reserved. MG07C102