5-30 Terminal 27 Digital Output [0] No operation All set-ups TRUE - Uint8
5-34 On Delay, Digital Output 0.01 s All set-ups TRUE -2 uint16
5-35 O Delay, Digital Output 0.01 s All set-ups TRUE -2 uint16
5-4* Relays
5-40 Function Relay ExpressionLimit All set-ups TRUE - Uint8
5-41 On Delay, Relay 0.01 s All set-ups TRUE -2 Uint16
5-42 O Delay, Relay 0.01 s All set-ups TRUE -2 Uint16
5-5* Pulse Input
5-50 Term. 29 Low Frequency 4 Hz All set-ups TRUE 0 Uint32
5-51 Term. 29 High Frequency 32000 Hz All set-ups TRUE 0 Uint32
5-52 Term. 29 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int32
5-53 Term. 29 High Ref./Feedb. Value ExpressionLimit All set-ups TRUE -3 Int32
5-55 Term. 33 Low Frequency 4 Hz All set-ups TRUE 0 Uint32
5-56 Term. 33 High Frequency 32000 Hz All set-ups TRUE 0 Uint32
5-57 Term. 33 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int32
5-58 Term. 33 High Ref./Feedb. Value ExpressionLimit All set-ups TRUE -3 Int32
5-6* Pulse Output
5-60 Terminal 27 Pulse Output Variable [0] No operation All set-ups TRUE - Uint8
5-62 Pulse Output Max Freq 27 5000 Hz All set-ups TRUE 0 Uint32
5-7* 24V Encoder Input
5-70 Term 32/33 Pulses Per Revolution 1024 N/A All set-ups FALSE 0 Uint16
5-71 Term 32/33 Encoder Direction [0] Clockwise All set-ups FALSE - Uint8
5-9* Bus Controlled
5-90 Digital & Relay Bus Control 0 N/A All set-ups TRUE 0 Uint32
5-93 Pulse Out 27 Bus Control 0 % All set-ups TRUE -2 Uint16
5-94 Pulse Out 27 Timeout Preset 0 % 1 set-up TRUE -2 Uint16
5.2.7 6-** Analog In/Out
Param
eter #
Parameter description Default value 4 set-up Change during
operation
Conversion
index
Type
6-0* Analog I/O Mode
6-00 Live Zero Timeout Time 10 s All set-ups TRUE 0 Uint8
6-01 Live Zero Timeout Function [0] O All set-ups TRUE - Uint8
6-1* Analog Input 53
6-10 Terminal 53 Low Voltage 0.07 V All set-ups TRUE -2 Uint16
6-11 Terminal 53 High Voltage 10 V All set-ups TRUE -2 Uint16
6-14 Terminal 53 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int32
6-15 Terminal 53 High Ref./Feedb. Value ExpressionLimit All set-ups TRUE -3 Int32
6-16 Terminal 53 Filter Time Constant 0.01 s All set-ups TRUE -2 Uint16
6-18 Terminal 53 Digital Input [0] No operation All set-ups TRUE - Uint8
6-19 Terminal 53 mode [1] Voltage mode 1 set-up TRUE - Uint8
6-2* Analog Input 54
6-20 Terminal 54 Low Voltage 0.07 V All set-ups TRUE -2 Uint16
6-21 Terminal 54 High Voltage 10 V All set-ups TRUE -2 Uint16
6-22 Terminal 54 Low Current 4 mA All set-ups TRUE -5 Uint16
6-23 Terminal 54 High Current 20 mA All set-ups TRUE -5 Uint16
6-24 Terminal 54 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int32
6-25 Terminal 54 High Ref./Feedb. Value ExpressionLimit All set-ups TRUE -3 Int32
6-26 Terminal 54 Filter Time Constant 0.01 s All set-ups TRUE -2 Uint16
6-29 Terminal 54 mode [1] Voltage mode 1 set-up TRUE - Uint8
6-9* Analog/Digital Output 42
6-90 Terminal 42 Mode [0] 0-20 mA All set-ups TRUE - Uint8
6-91 Terminal 42 Analog Output [0] No operation All set-ups TRUE - Uint8
Parameter Lists Programming Guide
MG07C102 Danfoss A/S © 12/2015 All rights reserved. 121
5 5

Other manuals for Danfoss VLT Midi Drive FC 280

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Midi Drive FC 280 and is the answer not in the manual?

Danfoss VLT Midi Drive FC 280 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Midi Drive FC 280
CategoryDC Drives
LanguageEnglish

Related product manuals