EasyManuals Logo
Home>Danfoss>DC Drives>VLT Midi Drive FC 280

Danfoss VLT Midi Drive FC 280 Programming Guide

Danfoss VLT Midi Drive FC 280
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #62 background imageLoading...
Page #62 background image
Selected
Event
Relay
output
On Delay
P 5-41
O Delay
P 5-42
130BA172.10
Illustration 4.11 O Delay, Relay
If the selected event condition changes before the on- or
o delay timer expires, the relay output is unaected.
4.6.4 5-5* Pulse Input
The pulse input parameters are used to dene an
appropriate window for the impulse reference area by
conguring the scaling and lter settings for the pulse
inputs. Input terminals 29 or 33 act as frequency reference
inputs. Set terminal 29 (parameter 5-13 Terminal 29 Digital
Input) or terminal 33 (parameter 5-15 Terminal 33 Digital
Input) to [32] Pulse input. If terminal 29 is used as an input,
then set parameter 5-01 Terminal 27 Mode to [0] Input.
130BD377.10
Ref.
Low freq.
P 5-50/
P 5-55
Input
(Hz)
High
ref.
value
P 5-53/
p 5-58
High freq.
P 5-51/
P 5-56
Low
ref.
value
P 5-52/
p 5-57
Illustration 4.12 Pulse Input
5-50 Term. 29 Low Frequency
Range: Function:
4 Hz* [4 - 31999
Hz]
Enter the low frequency limit corresponding
to the low motor shaft speed (that is low
reference value) in parameter 5-52 Term. 29
Low Ref./Feedb. Value. Refer to
Illustration 4.12.
5-51 Term. 29 High Frequency
Range: Function:
32000
Hz*
[5 - 32000
Hz]
Enter the high frequency limit
corresponding to the high motor shaft
speed (which is high reference value) in
5-51 Term. 29 High Frequency
Range: Function:
parameter 5-53 Term. 29 High Ref./Feedb.
Value.
5-52 Term. 29 Low Ref./Feedb. Value
Range: Function:
0* [-4999 -
4999 ]
Enter the low reference value limit for the motor
shaft speed [Hz]. This value is also the lowest
feedback value, see also parameter 5-57 Term. 33
Low Ref./Feedb. Value. Set terminal 29 to digital
input (parameter 5-02 Terminal 29 Mode=[0] Input
and parameter 5-13 Terminal 29 Digital
Input=applicable value.
5-53 Term. 29 High Ref./Feedb. Value
Range: Function:
Size
related*
[-4999 -
4999 ]
Enter the high reference value [Hz] for the
motor shaft speed, and the high feedback
value. See also parameter 5-58 Term. 33
High Ref./Feedb. Value. Select terminal 29
as a digital input (parameter 5-02 Terminal
29 Mode=[0] Input (default) and
parameter 5-13 Terminal 29 Digital
Input=applicable value).
5-55 Term. 33 Low Frequency
Range: Function:
4 Hz* [4 - 31999
Hz]
Enter the low frequency corresponding to
the low motor shaft speed (which is low
reference value) in parameter 5-57 Term. 33
Low Ref./Feedb. Value.
5-56 Term. 33 High Frequency
Range: Function:
32000
Hz*
[5 - 32000
Hz]
Enter the high frequency corresponding
to the high motor shaft speed (that is
high reference value) in
parameter 5-58 Term. 33 High Ref./Feedb.
Value.
5-57 Term. 33 Low Ref./Feedb. Value
Range: Function:
0* [-4999 -
4999 ]
Enter the low reference value [Hz] for the
motor shaft speed. This value is also the low
feedback value, see also parameter 5-52 Term.
29 Low Ref./Feedb. Value.
5-58 Term. 33 High Ref./Feedb. Value
Range: Function:
Size related* [-4999 -
4999 ]
Enter the high reference value [Hz]
for the motor shaft speed. See also
parameter 5-53 Term. 29 High Ref./
Feedb. Value.
Parameter Descriptions
VLT
®
Midi Drive FC 280
60 Danfoss A/S © 12/2015 All rights reserved. MG07C102
44

Other manuals for Danfoss VLT Midi Drive FC 280

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Midi Drive FC 280 and is the answer not in the manual?

Danfoss VLT Midi Drive FC 280 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Midi Drive FC 280
CategoryDC Drives
LanguageEnglish

Related product manuals