5.2.1 PROFIBUS DP-V1 Introduction
The PROFIBUS DP extension DP-V1 oers acyclic communi-
cation in addition to the cyclic data communication of DP
V0. This feature is possible using a DP master class 1 (for
example, PLC), as well as a DP master class 2 (for example
PC Tool).
Cyclic communication means that data transfer takes place
continuously with a certain refresh rate. This function is the
known DP V0 function normally used for quick updates of
I/O process data.
Acyclic communication is a
one-o data transfer event,
used for read/write from and to parameters from process
controllers, PC-based tools, or monitoring systems.
5.2.2 Features of a Master Class 1
Connection
Cyclic data exchange (DP-V0).
Acyclic read/write from and to parameters.
A master class 1 is used as the process controller (either
PLC or PC-based), responsible for commands, speed
reference, status of the application, and so on. The master
class 1 acyclic connection can be used for general
parameter access in the slaves. However, the acyclic
connection is xed and cannot be changed during
operation.
5.2.3 Features of a Master Class 2
Connection
Initiate/abort acyclic connection.
Acyclic read/write from and to parameters.
The master class 2 acyclic connection is typically used for
conguration or commissioning tools for easy access to
each parameter in any slave in the system. The acyclic
connection can be dynamically established (initiated) or
removed (aborted) even when a master class 1 is active on
the network.
5.2.4 Services Overview
Master
type
Service
Read Write Data
trans-
port
Initiate Abort Alarm
Read
data
from
slave
Write
data to
slave
Read
and
write
data
Open a
connec-
tion
Close a
connec-
tion
Master
class 1
Yes Yes Yes
Master
class 2
Yes Yes Yes Yes Yes
Table 5.1 Services Overview
5.2.5 Principle of Data Exchange by
PROFIBUS DP-V1
In a DP cycle, the master class 1 (MC1) rst updates the
cyclic process data for all slaves in the system. The MC1
then sends 1 acyclic message to 1 slave. If a master class 2
(MC2) is connected, the MC1 hands over the bus rights to
MC2. MC2 is then allowed to send 1 acyclic message to 1
slave. The token is then handed back to the MC1, and a
new DP cycle begins.
Illustration 5.1 DP Cycle
MC: Master class.
C1...Cn: Cyclic data.
AC1: Acyclic data master class 1.
AC2: Acyclic data master class 2.
PROFIBUS DP services are activated via specic service
access points (SAP). Table 5.2 shows the SAP specied for
acyclic communication.
Parameter Access
VLT
®
PROFIBUS DP MCA 101
26 Danfoss A/S © 01/2016 All rights reserved. MG37G202
55

Table of Contents

Other manuals for Danfoss VLT PROFIBUS DP MCA 101

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT PROFIBUS DP MCA 101 and is the answer not in the manual?

Danfoss VLT PROFIBUS DP MCA 101 Specifications

General IconGeneral
BrandDanfoss
ModelVLT PROFIBUS DP MCA 101
CategoryMedia Converter
LanguageEnglish

Related product manuals