8.5 Extended Diagnosis
Receive the extended diagnosis function, alarm, and
warning information from the frequency converter. The
setting of parameter 8-07 Diagnosis Trigger determines
which frequency converter events trigger the extended
diagnosis function:
•
When parameter 8-07 Diagnosis Trigger is set to [0]
Disable, no extended diagnosis data is sent
regardless of whether it appears in the frequency
converter or not.
•
When parameter 8-07 Diagnosis Trigger is set to [1]
Alarms, extended diagnosis data is sent when 1
or more alarms arrive in the alarm
parameter 16-90 Alarm Word or
parameter 9-53 Probus Warning Word.
When parameter 8-06 Reset Control Word Timeout is set to
[2] Alarms/Warnings, extended diagnosis data is sent if 1 or
more alarms/warnings arrive in the alarm
parameter 16-90 Alarm Word or parameter 9-53
Probus
Warning Word, or in the warning parameter 16-92 Warning
Word.
The extended diagnosis sequence is as follows:
If an alarm or warning appears, the frequency converter
sends a high-priority message to the master via the output
data telegram. The master then sends a request for
extended diagnosis information, to which the frequency
converter replies. When the alarm or warning disappears,
the frequency converter again sends a message to the
master, and on the following request from the master,
returns a standard DP diagnosis frame (6 bytes).
Byte Bit
number
Name
0–5 – Standard DP diagnosis data.
6 – PDU length.
7 0–7 Status type=0x81.
8 8–15 Slot=0.
9 16–23 Status information.
10 24–31 Parameter 16-90 Alarm Word.
11 32–39 Parameter 16-90 Alarm Word.
12 40–47 Parameter 16-90 Alarm Word.
13 48–55 Parameter 16-90 Alarm Word.
14 56–63 Reserved for future use.
15 64–71 Reserved for future use.
16 72–79 Reserved for future use.
17 80–87 Reserved for future use.
18 88–95 Parameter 16-92 Warning Word.
19 96–103 Parameter 16-92 Warning Word.
20 104–111 Parameter 16-92 Warning Word.
21 112–119 Parameter 16-92 Warning Word.
22 120–127 Reserved for future use.
23 128–135 Reserved for future use.
24 136–143 Reserved for future use.
25 144–151 Reserved for future use.
26 152–159 Parameter 9-53 Probus Warning Word.
27 160–167 Parameter 9-53 Probus Warning Word.
28 168–175 Reserved for future use.
29 176–183 Reserved for future use.
30 184–191 Reserved for future use.
31 192–199 Reserved for future use.
Table 8.18 Content of the Extended Diagnosis Frame
Troubleshooting Programming Guide
MG37G202 Danfoss A/S © 01/2016 All rights reserved. 59