Bit hex Dec Extended status word
(parameter 16-94 Ext.
Status Word)
0 00000001 1 Ramping
1 00000002 2 AMA running
2 00000004 4 Start CW/CCW
3 00000008 8 Slow down
4 00000010 16 Catch up
5 00000020 32 Feedback high
6 00000040 64 Feedback low
7 00000080 128 Output current high
8 00000100 256 Output current low
9 00000200 512 Output freq hgh
10 00000400 1024 Output freq low
11 00000800 2048 Brake check OK
12 00001000 4096 Braking max
13 00002000 8192 Braking
14 00004000 16384 Out of speed range
15 00008000 32768 OVC active
16 00010000 65536 AC brake
17 00020000 131072 Password timelock
18 00040000 262144 Password protection
19 00080000 524288 –
20 00100000 1048576 –
21 00200000 2097152 –
22 00400000 4194304 Unused
23 00800000 8388608 Unused
24 01000000 16777216 Unused
25 02000000 33554432 Unused
26 04000000 67108864 Unused
27 08000000 134217728 Unused
28 10000000 268435456 Unused
29 20000000 536870912 Unused
30 40000000 1073741824 Unused
31 80000000 2147483648 Unused
Table 8.15 Extended Status Word
Bit (hex) Unit
diagnose
bit
PROFIBUS warning word
(parameter 9-53 Probus Warning
Word)
00000001 160 Connection with DP-master is not OK.
00000002 161 Unused.
00000004 162 FDL (eldbus data link layer) is not OK.
00000008 163 Clear data command received.
00000010 164 Actual value is not updated.
00000020 165 Baud rate search.
00000040 166 PROFIBUS ASIC is not transmitting.
00000080 167 Initializing of PROFIBUS is not OK.
00000100 152 Frequency converter is tripped.
00000200 153 Internal CAN error.
00000400 154 Wrong conguration data from PLC.
00000800 155 Wrong ID sent by PLC.
00001000 156 Internal fault occurred.
00002000 157 Not congured.
00004000 158 Timeout active.
00008000 159 Warning 34, Fieldbus fault active
Table 8.16 Parameter 9-53 Probus Warning Word
Bit (hex) Communication option STW
(parameter 16-84 Comm. Option STW)
00000001 Parameterization OK.
00000002 Conguration OK.
00000004 Clear mode active.
00000008 Baud rate search.
00000010 Waiting for parameterization.
00000020 Waiting for conguration.
00000040 In data exchange.
00000080 Not used.
00000100 Not used.
00000200 Not used.
00000400 Not used.
00000800 MCL2/1 connected.
00001000 MCL2/2 connected.
00002000 MCL2/3 connected.
00004000 Data transport active.
00008000 Unused.
Table 8.17 Parameter 16-84 Comm. Option STW
NOTICE
Parameter 16-84 Comm. Option STW is not part of
extended diagnosis.
For diagnosis, read out the alarm words, warning words,
and extended status words via eldbus or optional
eldbus.
8.4
Fault Messages via DP Diagnosis
The standard DP function features an online diagnosis,
which is active during DP initialization and data exchange
mode.
Troubleshooting