7-2* Process Ctrl. Feedb
7-20 Process CL Feedback 1 Resource
*[0] >No function<
[1] >Analog Input 53<
[2] >Analog Input 54<
[3] >Frequency input 29<
[4] >Frequency input 33<
7-22 Process CL Feedback 2 Resource
7-3* Process PID Ctrl.
7-30 Process PID Normal/ Inverse Control
*[0] >Normal<
[1] >Inverse<
7-31 Process PID Anti Windup
[0] >Off<
*[1] >On<
7-32 Process PID Start Speed
>0 - 6000 rpm< *0 rpm
7-33 Process PID Proportional Gain
>0.00 - 10.00< *0.01
7-34 Process PID Integral Time
>0.10-9999.00 s< *9999.00 s
7-35 Process PID Differentiation Time
>0.00-20.00 s< *0.00 s
7-36 Process PID Diff. Gain Limit
7-38 Process PID Feed Forward Factor
>0-200%< *0%
7-39 On Reference Bandwidth
7-4* Adv. Process PID I
7-40 Process PID I-part Reset
7-41 Process PID Output Neg. Clamp
7-42 Process PID Output Pos. Clamp
7-43 Process PID Gain Scale at Min. Ref.
7-44 Process PID Gain Scale at Max. Ref.
7-45 Process PID Feed Fwd Resource
*[0] >No function<
[1] >Analog Input 53<
[2] >Analog Input 54<
[7] >Frequency input 29<
[8] >Frequency input 33<
[11] >Local bus reference<
[32] >Bus PCD<
7-46 Process PID Feed Fwd Normal/ Inv.
Ctrl.
7-48 PCD Feed Forward
7-49 Process PID Output Normal/ Inv. Ctrl.
7-5* Adv. Process PID II
7-50 Process PID Extended PID
7-51 Process PID Feed Fwd Gain
7-52 Process PID Feed Fwd Ramp up
7-53 Process PID Feed Fwd Ramp down
7-56 Process PID Ref. Filter Time
7-57 Process PID Fb. Filter Time
7-6* Feedback Conversion
7-60 Feedback 1 Conversion
*[0] >Linear<
[1] >Square root<
7-62 Feedback 2 Conversion
8-** Comm. and Options
8-0* General Settings
8-01 Control Site
8-02 Control Source
8-03 Control Timeout Time
8-04 Control Timeout Function
8-1* Ctrl. Word Settings
8-10 Control Word Profile
8-3* FC Port Settings
8-30 Protocol
*[0] >FC<
[2] >Modbus RTU<
8-31 Address
8-32 Baud Rate
[0] >2400 Baud<
[1] >4800 Baud<
*[2] >9600 Baud<
[3] >19200 Baud<
[4] >38400 Baud<
[5] >57600 Baud<
[6] >76800 Baud<
[7] >115200 Baud<
8-33 Parity / Stop Bits
*[0] >Even Parity, 1 Stop Bit<
[1] >Odd Parity, 1 Stop Bit<
[2] >No Parity, 1 Stop Bit<
[3] >No Parity, 2 Stop Bits<
8-35 Minimum Response Delay
8-36 Maximum Response Delay
8-37 Maximum Inter-char delay
8-4* FC MC protocol set
8-43 PCD Read Configuration
8-5* Digital/Bus
8-50 Coasting Select
8-51 Quick Stop Select
8-52 DC Brake Select
8-53 Start Select
8-54 Reversing Select
8-55 Set-up Select
8-56 Preset Reference Select
8-57 Profidrive OFF2 Select
8-58 Profidrive OFF3 Select
8-8* FC Port Diagnostics
8-80 Bus Message Count
8-81 Bus Error Count
8-82 Slave Messages Rcvd
8-83 Slave Error Count
8-84 Slave Messages Sent
8-85 Slave Timeout Errors
8-88 Reset FC port Diagnostics
13-** Smart Logic
13-0* SLC Settings
13-00 SL Controller Mode
*[0] >Off<
[1] >On<
13-01 Start Event
[0] >False<
[1] >True<
[2] >Running<
[3] >In range<
[4] >On reference<
[7] >Out of current range<
[8] >Below I low<
[9] >Above I high<
[16] >Thermal warning<
[17] >Mains out of range<
[18] >Reversing<
[19] >Warning<
[20] >Alarm (trip)<
[21] >Alarm (trip lock)<
[22] >Comparator 0<
[23] >Comparator 1<
[24] >Comparator 2<
[25] >Comparator 3<
[26] >Logic rule 0<
[27] >Logic rule 1<
[28] >Logic rule 2<
[29] >Logic rule 3<
[33] >Digital input DI18<
[34] >Digital input DI19<
[35] >Digital input DI27<
[36] >Digital input DI29<
*[39] >Start command<
[40] >Drive stopped<
[42] >Auto Reset Trip<
[50] >Comparator 4<
[51] >Comparator 5<
[60] >Logic rule 4<
[61] >Logic rule 5<
[83] >Broken Belt<
13-02 Stop Event
*[0] >Off<
[1] >On<
13-01 Start Event
[0] >False<
[1] >True<
[2] >Running<
[3] >In range<
[4] >On reference<
[7] >Out of current range<
[8] >Below I low<
[9] >Above I high<
[16] >Thermal warning<
[17] >Mains out of range<
[18] >Reversing<
[19] >Warning<
[20] >Alarm (trip)<
[21] >Alarm (trip lock)<
[22] >Comparator 0<
[23] >Comparator 1<
[24] >Comparator 2<
[25] >Comparator 3<
[26] >Logic rule 0<
[27] >Logic rule 1<
[28] >Logic rule 2<
[29] >Logic rule 3<
[30] >SL Time-out 0<
[31] >SL Time-out 1<
[32] >SL Time-out 2<
[33] >Digital input DI18<
[34] >Digital input DI19<
[35] >Digital input DI27<
[36] >Digital input DI29<
[39] >Start command<
*[40] >Drive stopped<
[42] >Auto Reset Trip<
[50] >Comparator 4<
[51] >Comparator 5<
[60] >Logic rule 4<
[61] >Logic rule 5<
[70] >SL Time-out 3<
[71] >SL Time-out 4<
[72] >SL Time-out 5<
[73] >SL Time-out 6<
[74] >SL Time-out 7<
[83] >Broken Belt<
13-03 Reset SLC
*[0] >Do not reset SLC<
[1] >Reset SLC<
13-1* Comparators
13-10 Comparator Operand
13-11 Comparator Operator
13-12 Comparator Value
13-2* Timers
13-20 SL Controller Timer
13-4* Logic Rules
13-40 Logic Rule Boolean 1
13-41 Logic Rule Operator 1
13-42 Logic Rule Boolean 2
13-43 Logic Rule Operator 2
13-44 Logic Rule Boolean 3
13-5* States
13-51 SL Controller Event
13-52 SL Controller Action
14-** Special Functions
14-0* Inverter Switching
14-01 Switching Frequency
[0] >Ran3<
[1] >Ran5<
[2] >2.0 kHz<
[3] >3.0 kHz<
[4] >4.0 kHz<
*[5] >5.0 kHz<
[6] >6.0 kHz<
[7] >8.0 kHz<
[8] >10.0 kHz<
[9] >12.0kHz<
[10] >16.0kHz<
14-03 Overmodulation
[0] >Off<
*[1] >On<
14-08 Damping Gain Factor
14-1* Mains On/Off
14-10 Mains Failure
*[0] >No function<
[1] >Ctrl. ramp-down<
>[2]< >Ctrl. ramp-down, trip<
[3] >Coasting<
[4] >Kinetic back-up<
[5] >Kinetic back-up, trip<
[6] >Alarm<
14-11 Mains Voltage at Mains Fault
14-12 Function at Mains Imbalance
*[0] >Trip<
[1] >Warning<
[2] >Disabled<
[3] >Derate<
14-15 Kin. Backup Trip Recovery Level
14-2* Reset Functions
14-20 Reset Mode
*[0] >Manual reset<
[1] >Automatic reset x 1<
[2] >Automatic reset x 2<
[3] >Automatic reset x 3<
[4] >Automatic reset x 4<
[5] >Automatic reset x 5<
[6] >Automatic reset x 6<
[7] >Automatic reset x 7<
[8] >Automatic reset x 8<
[9] >Automatic reset x 9<
[10] >Automatic reset x 10<
[11] >Automatic reset x 15<
[12] >Automatic reset x 20<
14-21 Automatic Restart Time
>0-600 s< *10 s
14-22 Operation Mode
*[0] >Normal operation<
[2] >Initialisation<
14-23 Typecode Setting
14-24 Trip Delay at Current Limit
14-25 Trip Delay at Torque Limit
14-27 Action At Inverter Fault
[0] >Trip<
*[1] >Warning or trip after warning<
14-28 Production Settings
14-29 Service Code
14-3* Current Limit Ctrl.
14-30 Current Lim Ctrl, Proportional Gain
14-31 Current Lim Ctrl, Integration Time
14-32 Current Lim Ctrl, Filter Time
14-4* Energy Optimising
14-40 VT Level
14-41 AEO Minimum Magnetisation
>40-75%< *66%
14-5* Environment
14-50 RFI Filter
14-51 DC-Link Voltage Compensation
14-52 Fan Control
*[5] >Constant-on mode<
[6] >Constant-off mode<
[7] >On-when-Inverter-is-on-else-off
Mode<
[8] >Variable-speed mode<
14-55 Output Filter
14-6* Auto Derate
14-63 Min Switch Frequency
*[2] >2.0 kHz<
[3] >3.0 kHz<
User Interface and Programm...
VLT
®
AutomationDrive FC 360 Quick Guide
26 MG06A102 - VLT
®
is a registered Danfoss trademark
44

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLTAutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLTAutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLTAutomationDrive FC 360
CategoryController
LanguageEnglish

Related product manuals