7-2* Process Ctrl. Feedb
7-20 Process CL Feedback 1 Resource
*[0] >No function<
[1] >Analog Input 53<
[2] >Analog Input 54<
[3] >Frequency input 29<
[4] >Frequency input 33<
7-22 Process CL Feedback 2 Resource
7-3* Process PID Ctrl.
7-30 Process PID Normal/ Inverse Control
*[0] >Normal<
[1] >Inverse<
7-31 Process PID Anti Windup
[0] >Off<
*[1] >On<
7-32 Process PID Start Speed
>0 - 6000 rpm< *0 rpm
7-33 Process PID Proportional Gain
>0.00 - 10.00< *0.01
7-34 Process PID Integral Time
>0.10-9999.00 s< *9999.00 s
7-35 Process PID Differentiation Time
>0.00-20.00 s< *0.00 s
7-36 Process PID Diff. Gain Limit
7-38 Process PID Feed Forward Factor
>0-200%< *0%
7-39 On Reference Bandwidth
7-4* Adv. Process PID I
7-40 Process PID I-part Reset
7-41 Process PID Output Neg. Clamp
7-42 Process PID Output Pos. Clamp
7-43 Process PID Gain Scale at Min. Ref.
7-44 Process PID Gain Scale at Max. Ref.
7-45 Process PID Feed Fwd Resource
*[0] >No function<
[1] >Analog Input 53<
[2] >Analog Input 54<
[7] >Frequency input 29<
[8] >Frequency input 33<
[11] >Local bus reference<
[32] >Bus PCD<
7-46 Process PID Feed Fwd Normal/ Inv.
Ctrl.
7-48 PCD Feed Forward
7-49 Process PID Output Normal/ Inv. Ctrl.
7-5* Adv. Process PID II
7-50 Process PID Extended PID
7-51 Process PID Feed Fwd Gain
7-52 Process PID Feed Fwd Ramp up
7-53 Process PID Feed Fwd Ramp down
7-56 Process PID Ref. Filter Time
7-57 Process PID Fb. Filter Time
7-6* Feedback Conversion
7-60 Feedback 1 Conversion
*[0] >Linear<
[1] >Square root<
7-62 Feedback 2 Conversion
8-** Comm. and Options
8-0* General Settings
8-01 Control Site
8-02 Control Source
8-03 Control Timeout Time
8-04 Control Timeout Function
8-1* Ctrl. Word Settings
8-10 Control Word Profile
8-3* FC Port Settings
8-30 Protocol
*[0] >FC<
[2] >Modbus RTU<
8-31 Address
8-32 Baud Rate
[0] >2400 Baud<
[1] >4800 Baud<
*[2] >9600 Baud<
[3] >19200 Baud<
[4] >38400 Baud<
[5] >57600 Baud<
[6] >76800 Baud<
[7] >115200 Baud<
8-33 Parity / Stop Bits
*[0] >Even Parity, 1 Stop Bit<
[1] >Odd Parity, 1 Stop Bit<
[2] >No Parity, 1 Stop Bit<
[3] >No Parity, 2 Stop Bits<
8-35 Minimum Response Delay
8-36 Maximum Response Delay
8-37 Maximum Inter-char delay
8-4* FC MC protocol set
8-43 PCD Read Configuration
8-5* Digital/Bus
8-50 Coasting Select
8-51 Quick Stop Select
8-52 DC Brake Select
8-53 Start Select
8-54 Reversing Select
8-55 Set-up Select
8-56 Preset Reference Select
8-57 Profidrive OFF2 Select
8-58 Profidrive OFF3 Select
8-8* FC Port Diagnostics
8-80 Bus Message Count
8-81 Bus Error Count
8-82 Slave Messages Rcvd
8-83 Slave Error Count
8-84 Slave Messages Sent
8-85 Slave Timeout Errors
8-88 Reset FC port Diagnostics
13-** Smart Logic
13-0* SLC Settings
13-00 SL Controller Mode
*[0] >Off<
[1] >On<
13-01 Start Event
[0] >False<
[1] >True<
[2] >Running<
[3] >In range<
[4] >On reference<
[7] >Out of current range<
[8] >Below I low<
[9] >Above I high<
[16] >Thermal warning<
[17] >Mains out of range<
[18] >Reversing<
[19] >Warning<
[20] >Alarm (trip)<
[21] >Alarm (trip lock)<
[22] >Comparator 0<
[23] >Comparator 1<
[24] >Comparator 2<
[25] >Comparator 3<
[26] >Logic rule 0<
[27] >Logic rule 1<
[28] >Logic rule 2<
[29] >Logic rule 3<
[33] >Digital input DI18<
[34] >Digital input DI19<
[35] >Digital input DI27<
[36] >Digital input DI29<
*[39] >Start command<
[40] >Drive stopped<
[42] >Auto Reset Trip<
[50] >Comparator 4<
[51] >Comparator 5<
[60] >Logic rule 4<
[61] >Logic rule 5<
[83] >Broken Belt<
13-02 Stop Event
*[0] >Off<
[1] >On<
13-01 Start Event
[0] >False<
[1] >True<
[2] >Running<
[3] >In range<
[4] >On reference<
[7] >Out of current range<
[8] >Below I low<
[9] >Above I high<
[16] >Thermal warning<
[17] >Mains out of range<
[18] >Reversing<
[19] >Warning<
[20] >Alarm (trip)<
[21] >Alarm (trip lock)<
[22] >Comparator 0<
[23] >Comparator 1<
[24] >Comparator 2<
[25] >Comparator 3<
[26] >Logic rule 0<
[27] >Logic rule 1<
[28] >Logic rule 2<
[29] >Logic rule 3<
[30] >SL Time-out 0<
[31] >SL Time-out 1<
[32] >SL Time-out 2<
[33] >Digital input DI18<
[34] >Digital input DI19<
[35] >Digital input DI27<
[36] >Digital input DI29<
[39] >Start command<
*[40] >Drive stopped<
[42] >Auto Reset Trip<
[50] >Comparator 4<
[51] >Comparator 5<
[60] >Logic rule 4<
[61] >Logic rule 5<
[70] >SL Time-out 3<
[71] >SL Time-out 4<
[72] >SL Time-out 5<
[73] >SL Time-out 6<
[74] >SL Time-out 7<
[83] >Broken Belt<
13-03 Reset SLC
*[0] >Do not reset SLC<
[1] >Reset SLC<
13-1* Comparators
13-10 Comparator Operand
13-11 Comparator Operator
13-12 Comparator Value
13-2* Timers
13-20 SL Controller Timer
13-4* Logic Rules
13-40 Logic Rule Boolean 1
13-41 Logic Rule Operator 1
13-42 Logic Rule Boolean 2
13-43 Logic Rule Operator 2
13-44 Logic Rule Boolean 3
13-5* States
13-51 SL Controller Event
13-52 SL Controller Action
14-** Special Functions
14-0* Inverter Switching
14-01 Switching Frequency
[0] >Ran3<
[1] >Ran5<
[2] >2.0 kHz<
[3] >3.0 kHz<
[4] >4.0 kHz<
*[5] >5.0 kHz<
[6] >6.0 kHz<
[7] >8.0 kHz<
[8] >10.0 kHz<
[9] >12.0kHz<
[10] >16.0kHz<
14-03 Overmodulation
[0] >Off<
*[1] >On<
14-08 Damping Gain Factor
14-1* Mains On/Off
14-10 Mains Failure
*[0] >No function<
[1] >Ctrl. ramp-down<
>[2]< >Ctrl. ramp-down, trip<
[3] >Coasting<
[4] >Kinetic back-up<
[5] >Kinetic back-up, trip<
[6] >Alarm<
14-11 Mains Voltage at Mains Fault
14-12 Function at Mains Imbalance
*[0] >Trip<
[1] >Warning<
[2] >Disabled<
[3] >Derate<
14-15 Kin. Backup Trip Recovery Level
14-2* Reset Functions
14-20 Reset Mode
*[0] >Manual reset<
[1] >Automatic reset x 1<
[2] >Automatic reset x 2<
[3] >Automatic reset x 3<
[4] >Automatic reset x 4<
[5] >Automatic reset x 5<
[6] >Automatic reset x 6<
[7] >Automatic reset x 7<
[8] >Automatic reset x 8<
[9] >Automatic reset x 9<
[10] >Automatic reset x 10<
[11] >Automatic reset x 15<
[12] >Automatic reset x 20<
14-21 Automatic Restart Time
>0-600 s< *10 s
14-22 Operation Mode
*[0] >Normal operation<
[2] >Initialisation<
14-23 Typecode Setting
14-24 Trip Delay at Current Limit
14-25 Trip Delay at Torque Limit
14-27 Action At Inverter Fault
[0] >Trip<
*[1] >Warning or trip after warning<
14-28 Production Settings
14-29 Service Code
14-3* Current Limit Ctrl.
14-30 Current Lim Ctrl, Proportional Gain
14-31 Current Lim Ctrl, Integration Time
14-32 Current Lim Ctrl, Filter Time
14-4* Energy Optimising
14-40 VT Level
14-41 AEO Minimum Magnetisation
>40-75%< *66%
14-5* Environment
14-50 RFI Filter
14-51 DC-Link Voltage Compensation
14-52 Fan Control
*[5] >Constant-on mode<
[6] >Constant-off mode<
[7] >On-when-Inverter-is-on-else-off
Mode<
[8] >Variable-speed mode<
14-55 Output Filter
14-6* Auto Derate
14-63 Min Switch Frequency
*[2] >2.0 kHz<
[3] >3.0 kHz<
User Interface and Programm...
VLT
®
AutomationDrive FC 360 Quick Guide
26 MG06A102 - VLT
®