5.5.2. Selecting the operating mode
To select an operating mode, proceed as follows:
1. Press the MODE key.
2. To select the desired parameter, turn the rotary button.
3. To modify the parameter, press the rotary button.
To go back to the previous display, press the key
j
.
4. To modify the parameter, turn the rotary button.
5. To confirm, press the rotary button.
To cancel, press key
h
.
MODE Menu
Parameter Adjustment range Description Factory setting
AUTOMATIQUE
The comfort ranges are determined by the timer programme.
DAY
7/7, xx:xx Comfort mode is forced until the time indicated or all the time (7/7). Present time + 1
hour
NIGHT
7/7, xx:xx Reduced mode is forced until the time indicated or all the time
(7/7).
Present time + 1
hour
HOLIDAYS
7/7, 1 to 364 The antifreeze mode is active on all boiler circuits.
Number of days’ holiday: xx
(1)
heating OFF: xx:xx
(1)
Restarting: xx:xx
(1)
Present date + 1
day
SUMMER
The heating is off.
Domestic hot water continues to be produced.
MANUEL
The generator operates according to the set point setting. All of
the pumps operate. Option of setting the set point by simply
turning the rotary button.
FORCE AUTO
(2)
YES / NO An operating mode override is activated on the remote control
(option).
To force all circuits to run on AUTOMATIQUE mode, select
YES.
(1) The start and end days and the number of days are calculated in relation to each other.
(2) The parameter is only displayed if a room sensor is connected.
5. Commissioning Diematic iSystem For C 330 / C 630 ECO
43
31082018 - 7600691-001-06