Operation
DeLaval milking point controller MPCII
94381001.pdf2006-07-20
F75 – Local mode
System
This function disconnects this place from
the bus, and the MPCII will work as a
Stand-alone if this parameter is set to 1.
The "communication interrupted" LED will
light up
- To connect to the bus, press F75↑ 0
again, the password is 6285.
F76 – Test mode
System and stand-alone
Pressing F, 7, 6, and ↑ on the MPCII sets
the MPCII in test mode.
If a rodreader is connected and there is
transponder within reading range, the
transponder number is displayed as "Txxxx".
As soon as the transponder is removed the
number will disappear from the display.
To finish, press F72 and ↑ or F2 ↑.
Test of inputs:Test of inputs:
1 = remote gate1 = remote gate
2 = Not used/HB; Photocell in the box/VT; box MPCII; photocell out right/VT, special MPCII; position
switch/Rot place MPCII
2 = Not used/HB; Photocell in the box/VT; box MPCII; photocell out right/VT, special MPCII; position
switch/Rot place MPCII
3 = remote release; VT special MPCII left side out/photocell; photocell special MPCII rotary3 = remote release; VT special MPCII left side out/photocell; photocell special MPCII rotary
4 = gate switch, installed at left side of the parlour; VT special MPCII Photocell/right side in4 = gate switch, installed at left side of the parlour; VT special MPCII Photocell/right side in
5 = gate switch, installed at right side of the parlour; VT special MPCII Photocell/left side in5 = gate switch, installed at right side of the parlour; VT special MPCII Photocell/left side in
Test of outputs:Test of outputs:
F700 Deactivates all outputsF700 Deactivates all outputs
F701 Activates output 1 (ACR cylinder)F701 Activates output 1 (ACR cylinder)
F702 Activates output 2 (ACR ISO)F702 Activates output 2 (ACR ISO)
F703 Activates output 3 (Duovac)F703 Activates output 3 (Duovac)
F704 Activates output 4 (auxiliary 1)F704 Activates output 4 (auxiliary 1)
F705 Activates output 5 (EP valve 1)F705 Activates output 5 (EP valve 1)
F706 Activates output 6 (EP valve 2)F706 Activates output 6 (EP valve 2)
F707 Activates output 7 (right gate valve)F707 Activates output 7 (right gate valve)
F708 Activates output 8 (left gate valve)F708 Activates output 8 (left gate valve)
F709 Activates output 9 (alarm lamp)F709 Activates output 9 (alarm lamp)
F710 Activates output 10 (auxiliary 2)F710 Activates output 10 (auxiliary 2)
F711 Activates output DCO/V (V COM) (only if EP50 is used)**F711 Activates output DCO/V (V COM) (only if EP50 is used)**
F715 Pulsator testF715 Pulsator test
F800 Deactivates all LEDsF800 Deactivates all LEDs
75(94)