Page #76 background image
EtherNet/IP Operation Manual
6-4
_6
Category Error Code Description How to fix them
16#11010123
The output connection
type parameters in the
EDS file are mismatched.
1. Check if the product information and the EDS file are
matched.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
16#11010124
The input connection type
parameters in the EDS file
are mismatched.
1. Check if the product information and the EDS file are
matched.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
16#11010125
The output redundant
ownership parameters in
the EDS file are
mismatched.
1. Check if the product information and the EDS file are
matched.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
16#11010126
The configuration size
parameters in the EDS file
are mismatched.
1. Check if the product information and the EDS file are
matched.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
16#11010129
The configuration path
parameters in the EDS file
are mismatched.
1. Check if the product information and the EDS file are
matched.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
16#11010132
The EDS file does not
support the Null forward
open.
1. Check if the product information and the EDS file are
matched.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
Data
Exchange
Setup Error
16#12010100
I/O Connections
Duplicated
1. Check if the system has created the I/O connections.
2. Change the connection type to Listen Only.
16#12010106
Ownership Conflict
1. Check the scanner owner.
2. Reconfigure the invalid scanner.
3. Change the connection to multicast.
16#12010110
Target for Connection not
Configured
1. Check the I/O connection status.
2. Activate the I/O connections again.
16#12010111
Adapter RPI Not
Supported
Check the RPI for the adapter.
16#12010113 Out of Connections
1. Check if the connection exceeds the limit.
2. Reduce the number of the product connection.
16#12010119
Non-Listen Only Not
Opened
1. Check if the system has created the I/O connections.
2. Check the scanner I/O connection status.
16#12010127
Invalid Originator to
Target Size
Check the module number and the product setup file to
see if they are matched.
16#12010128
Invalid Target to
Originator Size
Check the output size in the connection parameters.
16#1201012D
Consumed Tag does not
exist.
Check if the parameters in the consumed tag are
correctly set.
16#1201012E
Produced Tag does not
exist.
Check if the parameters in the produced tag are
correctly set.
16#12010204
Unconnected Request
Timeout
No response from the adapter; check if the power and
the network connection of the adapter are working
properly.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AHCPU560-EN2 Series and is the answer not in the manual?

Delta AHCPU560-EN2 Series Specifications

General IconGeneral
BrandDelta
ModelAHCPU560-EN2 Series
CategoryNetwork Hardware
LanguageEnglish

Related product manuals