Chapter 10 Function Cards
10-53
10
10.4 Wiring
10.4.1 AS-F2AD
Shielded cable *1
Shielded cable *1
2-wi re: c urre nt i nput
3-wire: v oltage in put
Shielded cable *1
Shielded cable *1
3-wire: c urrent i np ut
*1. Use shielded cables to isolate the analog input signal cable from other power cables.
*2. If the module is connected to a current signal, the terminals Vn and In+ (n=1–2) must be short-circuited.
*3. If variability in the input voltage results in interference within the wiring, connect the module to a capacitor having a
capacitance in the range of 0.10.47 μF and a working voltage of 25 V.
*4. Connect the shielded cable to the terminal FE.
*5. The wording CHXindicates that you can use the five wiring methods listed above for every input channel.