EasyManuals Logo
Home>Delta>Control Unit>AS200 Series

Delta AS200 Series User Manual

Delta AS200 Series
460 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #110 background imageLoading...
Page #110 background image
Chapter 2 Specifications and System Configuration
2-76
2_
AS-FPFN02
With its own standalone communication port, the extension card can work independently and can be set as a
PROFINET slave to connect to PROFINET network and exchange data with PROFINET master. After
installing the extension card, go to the PROFINET Configurator to set up the communication and download
the configurations to the master and then the master sends the configurations to the function card.
Wiring example
Linear Topology
2.10.2 Extension Card Profiles
AS-F2AD/AS-F2DA/AS-F422/AS-F485
37
23.9
59.3
60.8
1 5
Unit: mm
Pin no. AS-F2AD AS-F2DA AS-F422 AS-F485
1
V1+
VO1
R+
-
2
I1+
IO1
R-
-
3
V2+
VO2
T+
D+
4
I2+
IO2
T-
D-
5
COM
COM
SG
SG

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS200 Series and is the answer not in the manual?

Delta AS200 Series Specifications

General IconGeneral
BrandDelta
ModelAS200 Series
CategoryControl Unit
LanguageEnglish

Related product manuals