2.3 Digital Input/Output Module Specifications
2.3.1 General Specifications
Electrical specifications for the inputs on digital input/output modules
(The signals passing through the inputs are 24 VDC signals.)
Module name
08AM10N
-A
16AM10N
-A
32AM10N
-A
64AM10N
-A
16AP11R
A
16AP11T
-A
16AP11P
-A
Number of inputs
8
16
32
64
8
8
8
Connector type
Removable terminal
block
MIL connector Removable terminal block
Input type
Digital input
Input form
Direct current (sinking or sourcing)
Input voltage/ current
24 VDC5 mA
24 VDC
3.2 mA
24 VDC5 mA
Input impedance
4.7 k Ω 7.5k Ω 4.7 k Ω
Action level
OFFON
>15 VDC
ONOFF
<5 VDC
Response
time
OFFON
< 20 us
ONOFF
< 200 us
Software filter time
Setting range: 0 ~ 20 ms; default: 10 ms
Maximum input
frequency
Varies according to the filter time; for example when the filter is 1 ms, the
maximum input frequency is 500 Hz, when 2 ms, 250 Hz.
Note: CPU scan time also affects the maximum input frequency.
Input signal
Voltage input
Sinking: The inputs are NPN transistors whose collectors are open
collectors.
Sourcing: The inputs are PNP transistors whose collectors are open
collectors.
Electrical isolation
Optocoupler
Input display
When the optocoupler is driven, the input LED indicator is ON.
Weight
100 g
117 g
100 g
140 g
138 g
120 g
120 g
Electrical specifications for the outputs on a digital input/output module
Model
Item
08
AN01
R-A
16AN01
R-A
16AP11
R-A
08
AN01
T-A
16AN01
T-A
16AP11
T-A
08AN01
P-A
16AN01
P-A
16AP11
P-A
Number of outputs
8
16
8
8
16
8
8
16
8
Connector type
Removable terminal block
Output type
Digital output
Output form
Relay-R
Transistor-T (sinking)
Transistor-P (sourcing)
Voltage/ current
240 VAC/24 VDC
5–30 VDC
*2
5–30 VDC
*2
Leakage current
0uA <10uA
<250uA (@V1.00A0)
<10uA (@V1.00A1)
Maximum
load
Resistance
2A/output, 8A/COM
0.5A/output, 4A/COM 0.5A/output, 4A/COM
Inductance
Life cycle curve
*2
12 W (24 VDC)
12 W (24 VDC)
Bulb
20 W (24 VDC)
100 W (230 VAC)
2 W (24 VDC) 2 W (24 VDC)
Maximum
Resistance
1 Hz 100 Hz 100 Hz