Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-13-3
Group setting 04: Pump
The following table lists the relevant pump setting application parameters.
Pr. Explanation Settings
00-11 Speed Control Mode 0 (V/F control)
00-16 Duty Selection 0 (Normal load)
00-20
Master Frequency Command Source
(AUTO) / Source Selection of The PID
Target
2 (External analog input)
00-21 Operation Command Source (AUTO) 1 (External terminals)
00-23 Control of Motor Direction 1 (Disable reverse)
01-00 Maximum Operation Frequency Default setting
01-01 Motor 1 Rated / Base Frequency Default setting
01-02 Motor 1 Rated / Base Output Voltage Default setting
01-03 Motor 1 Mid-Point Frequency 1 Default setting
01-04 Motor 1 Mid-Point Voltage 1 Default setting
01-05 Motor 1 Mid-Point Frequency 2 Default setting
01-06 Motor 1 Mid-Point Voltage 2 Default setting
01-07 Motor 1 Minimum Output Frequency Default setting
01-08 Motor 1 Minimum Output Voltage Default setting
01-10 Output Frequency Upper Limit 50 (Hz)
01-11 Output Frequency Lower Limit 35 (Hz)
01-12 Acceleration Time 1 15 (s)
01-13 Deceleration Time 1 15 (s)
01-43 V/F Curve Selection 2 (Second V/F curve)
07-06 Restart after Momentary Power Loss
2 (Speed tracking by minimum output
frequency)
07-11 Number of Times of Restart After Fault 5
07-33 Auto-Restart Interval of Fault 60 (s)