Chapter 5 Parameters_VFD-B Series
Revision 10/2005, BE13, SW V4.08 5-43
02- 06
Line Start Lockout
Factory Setting: 00
Settings 00 Disable. Operation status is not changed even if operation command source
Pr.02-01 and/or Pr.02-14 is changed.
01 Enable. Operation status is not changed even if operation command source
Pr.02-01 and/or Pr.02-14 is changed.
02 Disable. Operation status will change if operation command source Pr.02-01
and/or Pr.02-14 is changed.
03 Enable. Operation status will change if operation command source Pr.02-01
and/or Pr.02-14 is changed.
This parameter determines the response of the drive when power on and operation command source is
changed.
Pr.02-06 Start lockout (Run when power is ON)
Operation status when operation
command source is changed
0 Disable (AC motor drive will run) Keep previous status
1 Enable (AC motor drive won’t run) Keep previous status
2 Disable (AC motor drive will run)
Change according to the new
operation command source
3 Enable (AC motor drive won’t run)
Change according to the new
operation command source
When the operation command source is from external terminal and operation command is ON (FWD/REV-
DCM=close), the AC motor drive will operate according to Pr.02-06 after power is applied. <For terminals
FWD and REV only>
1. When Pr.02-06 is set to 0 or 2, AC motor drive will run immediately.
2. When Pr.02-06 is set to 1 or 3, AC motor drive will remain stopped until operation command is received
after previous operation command is cancelled.