Chapter 1 IntroductionME300
1-7
Asymmetric Ground System (Corner Grounded TN Systems)
Caution: Do not remove the RFI jumper while there is power to the input terminal of the drive.
In the following four situations, you must remove the RFI jumper. This is to prevent the system from
grounding through the RFI and filter capacitors and damaging the drive.
You must remove the RFI jumper
1. Grounding at a corner in a triangle configuration
L2
L3
L1
2. Grounding at a midpoint in a polygonal
configuration
L2
L3
L1
3. Grounding at one end in a single-phase
configuration
L
1
N
4. No stable neutral grounding in a three-phase
autotransformer configuration
L1
L2
L3
L1
L2
L3
You can use the RFI jumper
Internal grounding through RFI capacitors that reduce
electromagnetic radiation. In a symmetrically grounding
power system with higher EMC requirements, install an
EMC filter. As a reference, the diagram on the right is a
symmetrical grounding power system.
L2
L
3
L
1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD5A5ME43ANNAA and is the answer not in the manual?

Delta VFD5A5ME43ANNAA Specifications

General IconGeneral
BrandDelta
ModelVFD5A5ME43ANNAA
CategoryDC Drives
LanguageEnglish

Related product manuals