Chapter 11 Summary of Parameter SettingsME300
11-15
03 Analog Input / Output Parameters
Pr. Explanation Settings Default
03-00
Analog input selection
(AVI)
0: No function
1: Frequency command
4: PID target value
5: PID feedback signal
6: PTC thermistor input value
11: PT100 thermistor input value
13: PID compensation value
1
03-03 Analog input bias (AVI)
-100.0
–100.0%
0.0
03-04 Analog input bias (ACI)
-100.0
–100.0%
0.0
03-07
Positive / negative
bias mode (AVI)
0: No bias
1: Lower than or equal to bias
2: Greater than or equal to bias
3: The absolute value of the bias voltage while serving as
the center
4: Bias serves as the center
0
03-08
Positive / negative
bias mode (ACI)
03-10
Reverse setting when
analog signal input is
negative frequency
0: Negative frequency input is not allowed. The digital
keypad or external terminal controls the forward and
reverse direction.
1: Negative frequency input is allowed.
Positive frequency = run in forward direction.
Negative frequency = run in reverse direction.
The digital keypad or external terminal control cannot
switch the running direction.
0
03-11 Analog input gain (AVI)
-500.0
–500.0%
100.0
03-12 Analog input gain (ACI)
-500.0
–500.0%
100.0
03-15
Analog input filter time
(AVI)
0.00–20.00 sec. 0.01
03-16
Analog input filter time
(ACI)
0.00–20.00 sec. 0.01
03-19
Signal loss selection for
analog input 4–20 mA
0: Disable
1: Continue operation at the last frequency
2: Decelerate to 0 Hz
3: Stop immediately and display “ACE”
0
03-20
Multi-function output
(AFM)
0: Output frequency (Hz)
1: Frequency command (Hz)
2: Motor speed (Hz)
3: Output current (rms)
4: Output voltage
5: DC BUS voltage
0