EasyManuals Logo
Home>Delta>DC Drives>VFD5A5ME43ANNAA

Delta VFD5A5ME43ANNAA User Manual

Delta VFD5A5ME43ANNAA
403 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #250 background imageLoading...
Page #250 background image
Chapter 12 Description of Parameter SettingsME300
12.1-03-17
Multi-function MO Output by AI Level Source
Default: 0
Settings 0: AVI
1: ACI
AI Upper Level 1
Default: 50
Settings -100–100%
AI Lower Level 2
Default: 10
Settings -100–100%
Multi-function output terminal 67 must work with Pr.03-44 to select input channels. When analog
input level is higher than Pr.03-45, multi-function output acts; when analog input level is lower
than Pr.03-46, multi-function output terminals stop outputting.
When setting levels, AI upper level must be higher than AI lower level.
Analog Input Curve Selection
Default: 0
Settings 0: Regular Curve
1: Three-point curve of AVI (& AI10)
2: Three-point curve of ACI (& AI11)
ACI Lowest Point
Default: 4.00
Settings Pr.03-28 ≠ 1, 0.00–20.00 mA
ACI Proportional Lowest Point
Default: 0.00
Settings Pr.03-28 ≠ 1, 0.00–100.00%
ACI Mid-point
Default: 12.00
Settings Pr.03-28 ≠ 1, 0.00–20.00 mA
ACI Proportional Mid-point
Default: 50.00
Settings Pr.03-28 ≠ 1, 0.00–100.00%
ACI Highest Point
Default: 20.00
Settings Pr.03-28 ≠ 1, 0.00–20.00 mA
ACI Proportional Highest Point
Default: 100.00
Settings Pr.03-28 ≠ 1, 0.00–100.00%

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD5A5ME43ANNAA and is the answer not in the manual?

Delta VFD5A5ME43ANNAA Specifications

General IconGeneral
BrandDelta
ModelVFD5A5ME43ANNAA
CategoryDC Drives
LanguageEnglish

Related product manuals