Chapter 12 Description of Parameter SettingsME300
12.1-07-4
Time
B.B. Speed tracking: from minimum output frequency
Input B.B. signal
Stop output voltage
Disable B.B. signal
Waiting time Pr. 07-08
Speed tracking
Synchronous speed detection
Output frequency (H)
Output voltage (V)
Output current
Pr. 07-09
Current level of
speed tracking
FWD Run
B.B.
A
B.B.
A
Time
Over-current stall prevention
Output frequency (H)
Output voltage (V)
Output current
Pr. 06-03
Over-current stall
prevention level
during accel.
FWD Run
Input B.B. signal
Stop output voltage
Disable B.B. signal
Waiting time Pr. 07-08
Speed tracking
Synchronous speed detection
Current Limit of Speed Tracking
Default: 100
Settings 20–200%
The AC motor drive executes speed tracking only if the output current is greater than the value
set in Pr.07-09.
The maximum current for speed tracking affects the synchronous time. The larger the parameter
setting is, the faster the synchronization occurs. However, if the parameter setting is too large,
the overload protection function may be activated.