EasyManuals Logo
Home>Delta>DC Drives>VFD5A5ME43ANNAA

Delta VFD5A5ME43ANNAA User Manual

Delta VFD5A5ME43ANNAA
403 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #303 background imageLoading...
Page #303 background image
Chapter 12 Description of Parameter SettingsME300
12.1-08-6
Parallel connection
Feedback Signal Detection Time
Default: 0.0
Settings 0.0–3600.0 sec.
Pr.08-08 is valid only for Pr.03-28=2 (4–20 mA).
This parameter sets the detection time for abnormal PID signal feedback. Setting the detection
time to 0.0 disables the detection function.
Feedback Signal Fault Treatment
Default: 0
Settings 0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: Warn and operate at last frequency
This parameter is valid only for Pr.03-28=2 (4–20 mA)..
The AC motor drive acts when the analog PID feedback is abnormal.
Sleep Frequency
Default: 0.00
Settings 0.00–599.00 Hz
Determines the sleep frequency, and if the sleep time and the wake-up frequency are enabled or
disabled.
Pr.08-10 = 0: Disabled
Pr.08-10 = ≠ 0: Enabled

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD5A5ME43ANNAA and is the answer not in the manual?

Delta VFD5A5ME43ANNAA Specifications

General IconGeneral
BrandDelta
ModelVFD5A5ME43ANNAA
CategoryDC Drives
LanguageEnglish

Related product manuals