Chapter 7 Optional AccessoriesME300
7-5
7-2 Non-fuse Circuit Breaker
Comply with the UL standard: Per UL 508, paragraph 45.8.4, part a.
The rated current of the breaker shall be 1.6–2.6 times of the maximum rated input current of the AC
motor drive.
Model Voltage/one-phase (three-phase)
Breaker Rating Input [A]
Heavy duty
VFD0A8ME11ANNAA
VFD0A8ME11ANSAA
115V / one-phase
20
VFD1A6ME11ANNAA
VFD1A6ME11ANSAA
20
VFD2A5ME11ANNAA
VFD2A5ME11ANSAA
25
VFD4A8ME11ANNAA
VFD4A8ME11ANSAA
50
VFD0A8ME21ANNAA
VFD0A8ME21AFNAA
VFD0A8ME21ANSAA
VFD0A8ME21AFSAA
230V / one-phase
15
VFD1A6ME21ANNAA
VFD1A6ME21AFNAA
VFD1A6ME21ANSAA
VFD1A6ME21AFSAA
15
VFD2A8ME21ANNAA
VFD2A8ME21AFNAA
VFD2A8ME21ANSAA
VFD2A8ME21AFSAA
20
VFD4A8ME21ANNAA
VFD4A8ME21AFNAA
VFD4A8ME21ANSAA
VFD4A8ME21AFSAA
30
VFD7A5ME21ANNAA
VFD7A5ME21AFNAA
VFD7A5ME21ANSAA
VFD7A5ME21AFSAA
45
VFD11AME21ANNAA
VFD11AME21AFNAA
VFD11AME21ANSAA
VFD11AME21AFSAA
70
VFD0A8ME23ANNAA
VFD0A8ME23ANSAA
230V / three-phase
15
VFD1A6ME23ANNAA
VFD1A6ME23ANSAA
15
VFD2A8ME23ANNAA
VFD2A8ME23ANSAA
15
VFD4A8ME23ANNAA
VFD4A8ME23ANSAA
15
VFD7A5ME23ANNAA
VFD7A5ME23ANSAA
25