NOTE At initial startup, input voltage auto-sensing is disabled by default. When manually
enabled by output voltage setting, at the next AC startup the UPS sets output
voltage according to input line voltage. After the subsequent startup, auto-sensing is
disabled until manually re-enabled by output voltage setting.
Installation
Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 25
14. If you installed an optional REPO, test the REPO function:
Activate the external REPO switch. Verify the status change on the UPS display.
Deactivate the external REPO switch and restart the UPS.
NOTE The internal batteries charge to 90% capacity in less than 3 hours. However, Eaton
recommends that the batteries charge for 48 hours after installation or long-term
storage
. If optional EBMs are installed, see the recharge times listed in Table 30 on
page 68.
15. Keep your UPS firmware updated. See “Updating the UPS Firmware” on page 52.