Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 26
Chapter 4 Operation
This chapter contains information on how to use the Eaton 9130, including front panel operation, operating
modes, UPS startup and shutdown, transferring the UPS between modes, retrieving the Event Log, setting the
power strategy, and configuring bypass settings, load segments, and battery settings.
Control Panel Functions
The UPS has a four-button graphical LCD with backlight. It provides useful information about the UPS itself,
load status, events, measurements, and settings (see Figure 17).
Power On Indicator (green)
On Battery Indicator (yellow)
Bypass Indicator (yellow)
Alarm Indicator (red)
On/Off Button
Escape Up Down Enter
esc
Figure 17. Eaton 9130 Control Panel
NOTE The button controls only the UPS output.
Table 1 shows the indicator status and description.
Table 1. Indicator Descriptions
Indicator Status Description
Green
On The UPS is operating normally.
Flashing A new information message is active.
Yellow
On The UPS is in Battery mode.
Flashing The battery voltage is below the warning level.
Yellow
On The UPS is in Bypass mode.
The UPS is operating normally on bypass during H
igh Efficiency operation.
Red
On The UPS has an active alarm or fault. See “Troubleshootin
g”on page 83 for additional
information.