Operation
Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 32
Standby Mode
When the UPS is turned off and remains plugged into a power outlet, the UPS is in Standby mode. The
indicator is off, indicating that power is not available to your equipment. The battery recharges when
necessary, and the communication bay is powered.
If utility fails and output turns off due to drained batteries or UPS
internal failure, the UPS alarms in Standby
mode and powers the communication bay for 1 hour 30 minutes or until battery voltage drops below 1.75 volts
per cell (whichever occurs first).
If utility fails while the UPS is in Standby mode, the l
ogic power supply turns off in approximately 10 seconds.
If the UPS is waiting on commands and utility fails, unit and logic power turn off in approximately 30 seconds.
UPS Startup and Shutdown
To start up or shut down the UPS, see:
l
“Starting the UPS” on page 32
l
“Starting the UPS on Battery” on page 32
l
“UPS Shutdown” on page 33
Starting the UPS
To start the UPS:
1. Verify that the UPS power cord is plugged in.
2. Switch on utility power where the UPS is connected.
The UPS front panel display illuminates and sho
ws a status of “UPS initializing…”.
3. Verify that the UPS transfers to Standby mode (“UPS on standby”).
4. Press the button on the UPS front panel for at least one second.
The UPS front panel display changes
status to “UPS starting…”.
5. Check the UPS front panel display for active alarms or
notices. Resolve any active alarms before
continuing. See “Troubleshooting” on page 83.
If the
indicator is on, do not proceed until all alarms are clear. Check the UPS status from the front
panel to view the active alarms. Correct the alarms and restart if necessary.
6. Verify that the
indicator illuminates solid, indicating that the UPS is operating normally and any loads
are powered.
The UPS should be in Normal mode.
7. Press the
button until the start screen appears.
Starting the UPS on Battery
NOTE 1 Before using this feature, the UPS must have been powered by utility power with
output enabled at least once.
NOTE 2 Battery start can be disabled. See the “Start on Battery” setting in “User Settings”
on page 28.