EasyManuals Logo
Home>Eaton>UPS>9130

Eaton 9130 User Manual

Eaton 9130
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
NOTE Leave
ribbon cable
connected.
Maintenance
Eaton 9130 700/3000 VA UPS User’s Guide 164201718—Rev 7 www.eaton.com/powerquality 46
Figure 23. Removing the UPS Right Front Cover
2. Disconnect the internal battery connector (see Figure 24).
3. Up
to 1500 VA models only. If the EBM cable is not connected to an EBM, unclip the EBM cable and
move it to the left out of the way (see Figure 24).
sledoM AV 00030002sledoM AV 0051 ot pU
Internal Battery
yrettaB lanretnIrotcennoC
Connector
EBM Cable
Battery Cover Plate Battery Cover Plate
Figure 24. Disconnecting the UPS Internal Batteries (Shown without EBMs)
4. Grasp an edge of the battery cover plate and pull it forward gently. Remove and retain the battery cover
plate. See Figure 24 for the location of the battery cover plate.
5. Carefully pull the handle on the battery tray and slide the battery package slowly out onto a flat, stable
surf
ace; use two hands to support the battery package. See “Recycling the Used Battery or UPS” on
page 52 for proper disposal.
NOTE Verify that the replacement batteries have the same rating as the batteries being
replaced.
6. Slide the new battery package into the cabinet. Push the battery package in firmly.
7. Replace the battery cover plate onto the screw mounts, threading the battery connector through the
access slot.

Table of Contents

Other manuals for Eaton 9130

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 9130 and is the answer not in the manual?

Eaton 9130 Specifications

General IconGeneral
BrandEaton
Model9130
CategoryUPS
LanguageEnglish

Related product manuals