32
Note:
①
UPS will shut down the charger and make an alarm, and the buzzer will beep continuously after 5
seconds.
②
The bypass LED will not be lit, and fault LED will be solid on with continuous beep;
③
The fault LED will be solid on with continuous beep;
④
The inverter LED will be lit, fault LED will ash with one beep every 1 second;
⑤
The fault LED will ash with one beep every 1 second;
⑥
The fault LED will ash with one beep every 1 second;
⑦●
: Indicator light is on
★
: Indicator light ashes
N
O.
Working
condition
Indicator
BUZZER LCD display
Inverter
LED
Battery
LED
Bypass
LED
Fault
LED
1 Line mode
Normal ●
none
Alarm
④
●
★
one beep every 1
second
Battery not connected/Charger
fault/Fan fault/LN connection
reversed or E not connected/
Bypass fault
Battery
overcharged
①
●
★
one beep every 1
second
Battery overcharged
2 Bypass mode
Normal ●
★
one beep every 2
mins
Alarm
★
one beep every 4
mins
Line fault
Alarm
⑤
●
★
one beep every 1
second
Battery not connected/
Charger fault/Fan fault/Battery
overcharged/LN connection
reversed or E not connected
Overload
②
●
★
two beeps every
1 second
Output overload
3 Battery mode
Normal ● ●
★
one beep every 4
seconds
Alarm ● ●
★
one beep every 1
second
Fan fault/LN connection
reversed or E not connected
Alarm ●
★ ★
one beep every 1
second
Low battery voltage
Overload
③
● ●
★
two beeps every
1 second
Output overload
4 Battery selftest mode
Normal
★ ★ ★ ★
none None
5 Fault mode
With bypass
output
● ●
continuous
beep
Fault type and alarm
Without bypass
output
●
continuous
beep
6 Standby mode
Normal none
Alarm
⑥
★
one beep every 1
second
Bypass fault/Line fault/Neutral
loss/Eeprom fault/Startup fail/
Parallel error/Address error/
Address conict
3.8 Display reference table