EasyManuals Logo
Home>Emerson>Measuring Instruments>Micro Motion

Emerson Micro Motion Installation Manual

Emerson Micro Motion
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
42 Micro Motion
®
Model D and DT Sensors Instruction Manual
Troubleshooting continued
Zero drift
Symptom
The flowmeter indicates the process fluid is flowing while flow is
stopped; or indicates a flow rate that does not agree with a reference
rate at low flow, but does agree at higher flow rates.
Troubleshooting instructions
To troubleshoot zero drift, you will need one of the communications
devices listed on page 46 or a transmitter with a display. Refer to the
table below for the necessary steps to troubleshoot zero drift.
Table 1. Troubleshooting zero drift
Procedure Instructions What to do next
1. Check for leaking valves and seals If no leaks are found, go to step 2
If leaks are found, eliminate them, then go to step 15
2. Check the flow units See page 46 If the flow units are OK, go to step 3
If the flow units are wrong, change them, then go to step 15
3. Make sure the flowmeter was
zeroed properly
See page 39 If the flowmeter was zeroed properly, go to step 4
If the flowmeter was not zeroed properly, zero it, then go
to step 15
4. Check for the proper flow
calibration factor
See page 49 If the flow cal factor is correct, go to step 5
If the flow cal factor is incorrect, change it, then go to step 15
5. Check the damping value See page 50 If the damping value is OK, go to step 6
If the damping value is too low, change it, then go to step 15
6. Check for two-phase flow See page 53 If there is no two-phase flow, go to step 7
If there is two-phase flow, fix the problem, then go to step 15
7. Check for moisture in the sensor
junction box
See page 52 If there is no moisture present, go to step 8
If there is moisture in the junction box, dry out and seal the
junction box, then go to step 15
8. Check for faulty or improperly
installed flowmeter wiring
See page 47 If the wiring is OK, go to step 9
If the wiring is faulty, fix or replace it, then go to step 15
9. Check for faulty or improperly
installed grounding
See page 51 If the grounding is OK, go to step 10
If the grounding is incorrect or faulty, fix it, then go to step 15
10. Check for mounting stress on the
sensor
See page 53 If the sensor mount is OK, go to step 11
If there are mounting stresses, fix it, then go to step 15
11. Check for vibration or crosstalk See page 53 If there is no vibration or crosstalk, go to step 12
If there is vibration or crosstalk, eliminate it, then go to
step 15
12. Make sure the sensor is oriented
properly
See page 13 If the sensor is oriented properly, go to step 13
If the sensor is not oriented properly, change the orientation,
then go to step 15
13. Check for plugging or build-up on
the sensor flow tubes
See page 54 If the tubes are not plugged, go to step 14
If there is plugging or build-up, clear the tubes, then go to
step 15
14. Check for RF interference See page 51 If there is no interference, or the source cannot be detected,
go to step 16
If there is interference, eliminate it, then go to step 15
15. Check again for zero drift If there is no longer any zero drift, you’ve solved the problem
If the zero drifts again, start over at step 3 or go to step 16
16. Contact Micro Motion Phone numbers are
listed on page 41

Other manuals for Emerson Micro Motion

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Micro Motion and is the answer not in the manual?

Emerson Micro Motion Specifications

General IconGeneral
BrandEmerson
ModelMicro Motion
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals