Service Mode General Operation of RLDS - UI • 45
Recommended Refrigerant Gas Alarm Settings
Gas
Alarm Settings (PPM)
Leak Spill Evacuate
CO
2
/R-744 1500 2000 3000
FA188 100 300 500
FC72 100 300 500
H1301 100 300 500
H1211 100 300 500
H2402 100 300 500
H1234YF 100 300 500
HFP 100 300 500
N1230 100 300 500
NH
3
/R-717 50 150 300
R11 100 300 500
R12 100 300 500
R21 100 300 500
R22 100 300 500
R23 100 300 500
R32 100 300 500
R113 100 300 500
R114 100 300 500
R123 25 35 50
R124 100 300 500
R125 100 300 500
R134A 100 300 500
R227 100 300 500
R236FA 100 300 500
R245FA 100 300 500
R401A 100 300 500
R402A 100 300 500
R402B 100 300 500
R404A 100 300 500
R407A 100 300 500
R408A 100 300 500
R407C 100 300 500
R409A 100 300 500
R410A 100 300 500
R422A 100 300 500
Table 8-1 - Recommended Alarm Settings and Gas Enumeration