Factory setting (depends on the country setup)
CO2 factor
Set the CO2 factor for the energy fed into the grid
Fan For testing the fan functionality
Setting range Test fan #1/test fan #2 (depending on the device)
-
Select the desired fan using the "Up" and "Down" keys
-
Pressing the "Enter" key starts the test for the selected fan.
-
The fan runs until the menu is exited by pressing the "Esc" key.
IMPORTANT! The inverter display does not indicate whether the fan is OK. The
fan function can only be checked by listening and feeling.
Arc Detection for checking arc detection/interruption
Setting range ArcDetector Status/Start Self-test
Arc.det. Status
displays the current status of arc detection/interruption
Start Self-test
self-test to check whether the inverter interrupts grid power feed operation
when an arc is detected.
Test procedure:
1
Select "Arc Detection" in the Setup menu
2
Press the "Enter" key
3
Use the up and down keys to select "Start Self-test"
4
Press the "Enter" key
The self-test starts. The arc detection/interruption function simulates an arc
and sends the corresponding signal to the inverter.
If the test is successful, the inverter disconnects from the grid and stops grid
power feed operation.
The message "Self-test completed and Start AFCI" is shown on the display.
5
Confirm the indication by pressing the "Enter" key
40