Packaging - Shipping and storage
Packaging - Identification - Storage
GE Information L22- 027EN/04
6/6
03- 2017
Storage, continued
Medium- term storage
(less than 2 years)
The table below indicate how to stock the main components of the
circuit- breaker for a medium- term storage :
Centralizing cubicle
The centralizing cubicle should be
stored in the same place as the
circuit- breaker and the operating
device, these three sub- assemblies
being inseparable.
S In order to prevent corrosion
damage due to formation of
condensation, it is mandatory that the
heating circuit be switched on. Put
vetically the centtralizing cubicle for
that air can enter through the vents.
ANY CHANGE OF LOCATION OF THE APPARATUS (EVEN AFTER
COMMISSIONING) SHOULD BE DONE AT A REDUCED PRESSURE OF
0.03 MPa.