4-84
2nd
entry
</ENT
or
</ENT
Set Password successfully
Set Password failed
or
</ENT
The Parameter Lock Key Code STATUS become: 00002. User has no access to
parameters setting.
2.3 After step 2.2, the procedure to UNLock the access to all parameters is the following:
Lifting
Password
</ENT
or
</ENT
Password successfully lifted
Password failed to lift
or
</ENT
3. Lost password recovery
If a password set by customer is lost, please contact Gefran Service Team for assistance.
13- 08
Reset Drive to Factory Settings
Range
1150
: Reset to factory setting (50Hz,220V/380V system)
1160
: Reset to factory setting (60Hz,220V/380V system)
1250
: Reset to factory setting (50Hz,230V/400V system)
1260
: Reset to factory setting (60Hz,230V/460V system)
1350
: Reset to factory setting (50Hz,220V/415V system)
1360: Reset to factory setting (60Hz,230V/400V system)
When a Parameter lock key number has been entered in parameter 13 07. This key
number must be entered first before parameter 13-08 can be used.
Reset 13-08 to default setting will reset parameter 02 group.
For built-in EMC filter models, the default setting of 13-08 is “1250”.
For without built-in EMC filter models, the default setting of 13-08 is “1360”