5-1
Chapter 5 Troubleshooting and maintenance
5.1 Error display and corrective action
5.1.1 Manual Reset and Auto-Reset
Faults which cannot be recovered manually
Voltage too high
when stopped
Detection circuit malfunction Consult with the supplier
Voltage too low
when stopped
1. Power voltage too low
2. Pre-charge resistor or fuse
burnt out.
3. Detection circuit malfunction
1. Check if the power voltage
is correct
2. failed resistor or fuse
3. Consult with the supplier
The inverter is
overheated when
stopped
1. Detection circuit
malfunction
2. Ambient temperature too
high or bad ventilation
Improve the ventilation
conditions, if no result then
replace the inverter
OH-C
The inverter is
overheated during
running
1. IGBT temperature is too
high or poor ventilation
2. temperature sensor error or
circuit malfunctions
frequency
2. Improve the ventilation
conditions, if no result then
Current Sensor
detection error
Current sensor error or
circuit malfunction
Consult with the supplier
setting error:
Inverter capacity
setting 13-00
does not match
The inverter capacity setting
(13-00) does not match the
hardware voltage levels
Check the inverter capacity
setting (13-00) to meet the
hardware voltage levels.
CPU Unusual
interruption
External noise interference
1. Remove the interference
source then restart by
switching power OFF/ON
2. If not resolved then Consult
EEPROM
problem
Faulty EEPROM Consult with the supplier
Communication
error
Communications disruption Check the wiring