5-7
5.3 Routine and periodic inspection
To ensure stable and safe operations, check and maintain the inverter at regular intervals.
Use the checklist below to carry out inspection.
Disconnect power after approximately 5 minutes to make sure no voltage is present on the output terminals
before any inspection or maintenance.
Items Details
Methods Criteria Remedies
Environment & Ground connection
Ambient
conditions at
the installation
Confirm the temperature
and humidity at the machine
◎
Measure with
thermometer
and
hygrometer
-10 ~40°C
(14~120°F)
Humidity:
Below
Improve the
ambient or
relocate the
drive to a
better area.
Installation
Grounding
Is the grounding resistance
correct?
◎
resistance
with a
200Vclass:
below 100Ω
Improve the
grounding if
needed.
Connection
terminals
Any loose parts or
terminals?
◎
Visual check
Check with a
screwdriver
Correct
installation
requirement
Secure
terminals and
remove rust
◎
Wiring
◎
Visual check
Correct wiring
requirement
Rectify as
necessary
Any damage to the wire
insulation?
◎
Input power
voltage
Is the voltage of the main
circuit correct?
◎
voltage with a
conform with
voltage if
Circuit boards and components
Printed circuit
board
damage to printed circuit
◎
Visual check
Correct
component
condition
replace the
Power
component
Any dust or debris
◎
Check resistance between
terminals
◎
Measure with
a multi-tester
circuit or
broken circuit
in three
Consult with
the supplier
Cooling fan
Unusual vibration and
noise?
◎
Correct
cooling
Consult with
the supplier
◎
Visual check
Heat sink Excessive dust or debris
◎
Ventilation Path
Is the ventilation path
blocked?
◎
Clear the
path